Refco DIGIMON-SE Guide D'installation Et D'utilisation page 21

By-pass electronique
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Instruction Manual DIGIMON-SE / DIGIMON4
9.
Press the
from Point 6
10. Once both sensors are calibrated, press
mode.
Calibrating the temperature sensors / clamps (0°C / 32°F ice water)
1. Switch off the DIGIMON
2. Plug in the thermocouples (K-type).
The DIGIMON and the thermocouples must remain at a constant room
temperature for at least 20 minutes. The thermocouple cables must be straight
(unwound).
3. While holding down the
pressing the
the display shows, "Password" 000
4. Press the
5. Press the
 Display shows "T-call0"
6. Press the
temperature sensor/clamp calibration mode.
During calibration, ensure that both thermocouples are well connected to the
DIGIMON.
 The display shows
LP
011xx
24.4°C
-
R
button to calibrate the high pressure side (HP)  Repeat
LIGHT
ON/OFF
button once. Continue holding down the Light button until
+
-
R
R
buttons to scroll to code number 020.
/
SET
button once.
-
R
button once and then press the
ON/OFF
button continuously, switch on the device by
(low pressure side)
Temperature code (will change)
Your temperature reading (will not change)
to exit the sensor calibration
SET
button once to enter
English
19

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Digimon4

Table des Matières