PRE-INSTALLATION WARNINGS
1. The Field Controls Oil Vent Damper must be installed by a qualified agency in accordance with the
manufacturer's installation instructions. The definition of a qualified agency is: any individual, firm, corporation
or company which either in person or through a representative is engaged in, and is responsible for, the
installation and operation of oil burning appliances, is experienced in such work, familiar with all the precautions
required, and has complied with all the requirements of the authority having jurisdiction. The oil vent damper is
designed to service one appliance only.
2. The qualified agency shall fill in the agencies name, address and installation date on the label attached to the
vent damper device.
3. The Field Controls automatic oil vent damper can only be installed on automatically operated oil appliances that
utilize atomizing power oil burners.
4. The Field Controls automatic oil vent damper must not be installed on oil appliances utilizing a direct vent
system, sealed combustion system or vaporizing type burners.
5. Do not override the action of any existing safety or operational controls.
6. When servicing controls, all wires must be LABELED prior to disconnection. Wiring errors can cause improper
and dangerous operation.
7. Device must be installed by a qualified agency, in accordance with the following standards:
In the US
In Canada
8. The maximum temperature of the selected location must not exceed 1000 degrees F (538°C) Measure the flue
gas temperature at the appliance flue collar.
9. Install downstream from the appliance draft control, as close to the draft control as practical, and without
modification to the draft control or the vent damper unit.
10. Locate the WMO-1 between the draft control and the flue collar of the single appliance for which it services.
11. Locate damper in a venting system or section of a venting system so that it services only the single appliance
for which it is intended.
12. A minimum clearance of 18 inches (457 mm) between the damper device and combustible construction must be
maintained and that there be provisions for access and service of the damper device.
13. Position indicator and service switch must be accessible to the user.
14. This device must be installed only on a oil appliance connected to a factory built chimney or vent system
complying with a recognized standards, or a masonry or concrete chimney lined with a lining material
acceptable to the authority having jurisdiction.
P
-
RE
INSTALLATION INSPECTIONS
P
F
S
ROCEDURE
OR
AFETY
The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in a
safe condition for continuing use.
This procedure is predicated on central furnace, boiler and water heater installations, and it should be recognized
that generalized procedures cannot anticipate all situations. Accordingly, in some cases deviation from this
procedure may be necessary to determine safe operation of the equipment.
1. This procedure shall be performed prior to installation of the automatic vent damper system.
2. If it is determined there is a condition which could result in unsafe operation, the appliance should be shut
off and the owner advised of the unsafe condition. Do not install the automatic vent damper system until the
unsafe condition has been corrected.
NFPA 31 Standard for the Installation of Oil -Burning Equipment
NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances
NFPA 70 National Electric Code
CSA B139 Installation Code for Oil Burning Equipment
C22.1 Canadian Electrical Code Part 1
I
O
A
E
NSPECTION
F
N
XISTING
A
I
PPLIANCE
NSTALLATION
3