Safety Technique
SAFEMASTER
Extension module
BN 3081
Product Description
If more safety cicuits have to be switched, than a safety module provides,
the extension module BN 3081 is used. It offers safe and reliable contact
multiplication and re-enforcment for safety modules with monitoring of the
feedback circuit. Safe semiconductor outputs can be extended by relay
output contacts. The extension module has forcibly guided contacts and
can be delivered with different contact arrangements.
Block Diagram
A1
A3
K1
K2
K1
M6362
A2
A4
Circuit Diagram
A1 A3 13 23 33 43 53 63 73 81
A1 A3
13 23 33 43 53 63 73 81
K1
K2
A2 A4
14 24 34 44 54 64 74 82
A2 A4 14 24 34 44 54 64 74 82
M7395_b
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
13
23
33
43
53 63 73 81
K1
K2
K2
14
24
34
44
54
64 74 82
Your Advantages
• Safety contact multiplication
Features
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
when connected to a suitable safety module
• Redundant and forcibly guided contacts
• Output: 7 NO contacts, 1 NC contact for feed back circuit
• 1- or 2-channel connection
• LED displays for channels 1.2
• Removable terminal strips
• Width 100 mm
Approvals and Markings
* see variants
Applications
Contact multiplication of emergency-stop modules and safety door monitors.
Indication
LED K1:
LED K2:
Connection Terminals
Terminal designation
A1 (+), A3 (+)
A2, A4
13, 14, 23, 24, 33, 34, 43, 44,
53, 54, 63, 64, 73, 74
81, 82
13
*
Canada / USA
A025518
on when supply on relay K1
on when supply on relay K2
Signal description
+ / L
- / N
Forcibly guided NO contacts for
release circuit
Forcibly guided feedback circuit
BN 3081 / 25.09.18 en / 022A