Item
(6)
(7)
(8)
(9)
Example
Recording and archiving data from the inverter and sensor using a Fronius Datamanager
and a Fronius Sensor Box:
Data network with 3 inverters and a Fronius Sensor Box:
- Inverter 1 with Fronius Datamanager
- Inverters 2 and 3 without Fronius Datamanager!
The external communication (Fronius Solar Net) takes place on the inverter via the data
communication area. The data communication area contains two RS 422 interfaces as in-
puts and outputs. RJ45 plug connectors are used to make the connection.
IMPORTANT! Since the Fronius Datamanager functions as a data logger, the Fronius So-
lar Net ring must not include any other data logger.
Only one Fronius Datamanager per Fronius Solar Net ring!
Designation
USB A socket
for connecting a USB stick with maximum dimensions of
65 x 30 mm
The USB stick can function as a datalogger for an inverter. The USB stick is not
included in the scope of supply of the inverter.
Floating switch contact with mating connector
max. 250 V AC / 4 A AC
max. 30 V DC / 1 A DC
max. AWG16 (1.5 mm²) cable cross section
Pin 1 = NC contact
Pin 2 = common
Pin 3 = NO contact
(pins from top to bottom)
Use the mating connector supplied with the inverter to connect to the floating
switch contact.
Fronius Datamanager with WLAN antenna
or
another Fronius plug-in card
or
Cover for option card compartment
Cover for option card compartment
IN
WLAN
* Fronius Datamanager
= Terminating plug
1
2
*
IN
OUT
OUT
°C
3
Sensor Box
IN
OUT
OUT
IN
m/s
W/m²
31