Mitsubishi Electric CITY MULTI CMB-P104V-G1 Manuel D'installation page 2

Appareil intérieur, contrôleur bc principal, contrôleur bc secondaire
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
2
2.2
[Fig. 2.2.1]
A Inspection hole
B On the side of outdoor unit piping
C Control box
D On the side of indoor unit piping
*1 Dimensions with which pipe connection can be handled at site
[Fig. 2.4.1]
CMB-P104, 105, 106, 108, 1010, 1013, 1016G1 (In the case the outdoor unit is 14-hp (P350 model) or less, and 16 or fewer ports are used.)
A
I
A
H
a
C
A Outdoor unit
C Indoor unit
E Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G Twinning pipe (for Y Series) CMY-Y102S-G2
H Combined pipe (CMY-R160-J1: optional)
I Less than 110 m
K Up to three units for 1 branch hole
Total capacity: less than 80 (but same in cooling/heating mode)
L Less than h1=15 m (10 m or less for 200, 250 unit type)
M Less than h2=15 m
Item
Total piping length
Longest piping length
Between outdoor unit and
BC controller
Between indoor units and BC controller
Above outdoor unit
Between
indoor and
Below outdoor unit
outdoor units
Between indoor units and BC controller
Between indoor units
2
<A>
B
200
B
J
G
b
B
c
d
e
C
C
C
D
K
C
B BC controller
D P100 - P250 model: 2 ports merged.
J Less than 40 m
Piping portion
Allowable value
Not to exceed the
A+B+a+b
maximum refriger-
+c+d+e
ant piping length *1
165 m or less
(Equivalent length
A+e
of 190 m or less)
A
Below 110
e
Below 40 *2
H
Below 50
H1
Below 40
Below 15
h1
(Below 10)*3
Below 15
h2
(Below 10)*3
[Fig. 2.3.1]
200
B
A
450
C
D
INDOOR UNIT SIDE
A
2.4
Notes:
*1 Refer to "Restrictions on piping length" on P. 4.
*2 Please refer to the figure "Distance between BC controller and farthest
Indoor unit" when the distance between BC controller and farthest in-
door unit exceeds 40 m. (Not applicable to the P250 model indoor unit)
*3 The values in the parentheses show the maximum piping length to be
followed when the connection capacity of the indoor unit is 200 or more.
*4 In the system to which indoor units of the P200 model or above are con-
nected, neither a branch joint nor a branch header may be used.
*5 Do not connect the P200 or P250 models of indoor units and other mod-
els of indoor units at the same port.
*6 In the system to which indoor units of the P100 through P140 models are
connected, merge the two ports before connecting them. (Set DIP SW4-6
on the BC controller to ON.)
*7 It is possible to connect the P100 through P140 models of indoor units to
a single port. (Set DIP SW4-6 to OFF.) Note that the cooling capacity will
somewhat decrease. (The factory setting for DIP SW4-6 is OFF.)
*8 Indoor units that are connected to the same branch joint cannot be si-
multaneously operated in different operation modes.
Distance between BC controller
and farthest indoor unit
70
60
50
40
30
(Unit: m)
20
10
0
0
5
Height difference between
BC controller and farthest
indoor unit (m)
2.3
<B>
B
Model name
A
CMB-P104V-G1
CMB-P105V-G1
CMB-P106V-G1
648
CMB-P108V-G1
CMB-P1010V-G1
CMB-P1013V-G1
1098
CMB-P1016V-G1
CMB-P108V-GA1
CMB-P1010V-GA1
1110
CMB-P1013V-GA1
CMB-P1016V-GA1
CMB-P104V-GB1
648
CMB-P108V-GB1
CMB-P1016V-HA1
1110
CMB-P1016V-HB1
1098
10
15
<A> Top view
<B> Front view
B
-
200
-
200
-