10. Trouble shooting
Please verify in advance if pressure is being applied (valves/ ball valve etc. open) and if the
right voltage supply and the right type of wiring (2-wire/ 3-wire) has been chosen?
Failure
Possible cause
No/incorrect voltage supply or current
No output signal
spike
Cable break
Incorrectly wired (e.g. Connected as
No/False output signal
2-wire instead of 3-wire system)
Abnormal output signal
Span incorrectly adjusted
Zero point set wrongly
Output signal unchanged after change
Mechanical overload through over-
in pressure
pressure
Wrong supply voltage or current spike
Signal span too small
Power supply too high/too low
Signal span drops off
Moisture present (e.g. at the cable tail) Install the cable correctly
Electromagnetic interference source in
Signal span erratic
the vicinity, e.g. inverter drive
Instrument not grounded
Strong fluctuations in the power supply
In case of unjustified reclamation we charge the reclamation handling expenses.
*)
Make sure that after the setting the unit is working properly. In case the error continues to exist send in the instrument for reparation (or
replace the unit).
14
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi SL-1
GB
Procedure
Adjust the voltage supply to correspond
with the Operating Instructions *)
Check connections and cable
Follow pin assignment (see Instrument
Label / Operating Instructions)
Use appropriate reference
Use correct calibration equipment (at
least 3x the accuracy of the quoted
accuracy)
Replace instrument; if failure reoccurs,
consult the manufacturer *)
Replace instrument
Correct the power supply in line with
the Operating Instructions
Shield the device; shield the cables;
remove the interference source.
Ground instrument
Stabilise the power supply; smooth it
(i.e.; remove interferences)
10. Trouble shooting / 11. Storage, disposal
If the problem persists, contact our sales department.
USA, Canada
If the problem continues, contact WIKA or an authorized agent for assistance. If the pres-
sure transmitter must be returned obtain an RMA (return material authorization) number and
shipping instructions from the place of purchase. Be sure to include detailed information about
the problem. Pressure transmitters received by WIKA without a valid RMA number will not be
accepted.
Process material certificate (Contamination declaration for returned goods)
Clean dismounted instruments before returning them in order to protect our employees and
the environment from any hazard caused by adherent remaining media.
Service of instruments can only take place safely when a Product Return Form has been
submitted and fully filled-in. This Return Form contains information on all materials with which
the instrument has come into contact, either through installation, test purposes, or cleaning.
You can find the Product Return Form on our internet site (www.wika.de / www.wika.com).

11. Storage, disposal

When storing or disposing of the pressure transmitter, take precautions with
!
regard to remaining media in removed pressure transmitters. We recom-
mend cleaning the transmitter properly and carefully. Remaining media in
Warning
the pressure port may be hazardous or toxic!
Disposal
Dispose of instrument components and packaging materials in accordance with the
respective waste treatment and disposal regulations of the region or country to which
the instrument is supplied.
WIKA reserves the right to alter these technical specifications.
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi SL-1
GB
15

Publicité

Table des Matières
loading

Table des Matières