8. Adjustment of zero point / span

8. Adjustment of zero point / span (only for pressure transmitter with
clamping nut)
We do not recommend to adjust the span potentiometer. It is used for adjustment ex
factory and should not be adjusted by you unless you have adequate calibration equip-
ment at your disposal (at least three times more accurate than the instrument being
tested).
Make sure wires are not cut or pinche
during disassembly and reassembly of
the connector.
Remove the female connector. Open
the pressure transmitter by detaching
the clamping nut (see Fig. A ). Carefully
remove the male connector from the
case.
Adjust the zero point (Z) (see Fig. B ) by
generating the lower limit of the pressure
range.
Adjust the span (S) by generating the
higher limit of the pressure range.
Check the zero point.
If the zero point is incorrect, repeat
procedure as required.
Reassemble the instrument carefully.
Make sure all sealings and o-rings are
not damaged and correctly installed to
assure the rated moisture ingress protec-
tion.
Recommended recalibration cycle: 1 year
12
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi SL-1
Female
connector
Sealing
Clamping
nut
Male
connector
Sealing
S = Span
Z = Zero
Case with
pressure
A
connection
For further information (+49) 9372/132-8976
GB
9. Maintenance, accessories / 10. Trouble shooting

9. Maintenance, accessories

WIKA pressure transmitters require no maintenance.
Have repairs performed by the manufacturer only.
Accessories
For details about the accessories (e. g. connectors), please refer to WIKA's price list, WIKA's
product catalog on CD or or contact our sales department.

10. Trouble shooting

B
Open pressure connections only after the system is without pressure!
!
Warning
Take precautions with regard to remaining media in removed pressure trans-
!
mitters. Remaining media in the pressure port may be hazardous or
toxic!
Warning
Remove the pressure transmitter from service and mark it to prevent it from
being used again accidentally, if it becomes damaged or unsafe for opera-
tion.
Have repairs performed by the manufacturer only.
Do not insert any pointed or hard objects into the pressure port for cleaning to prevent
damage to the diaphragm of the pressure connection.
Do not clean the pressure port with liquids or compressed air!
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi SL-1
GB
13