GKR/GKL Series
Designation and
Rated Operational Current Ie (A) at Rated Operational Voltage Ue (V)
Utilization Category
AC15
A300
DC13
Q300
Rated Thermal Current (I
)
th
Rated Impulse Withstand (U
Rated Insulation Voltage (Ui)
Sealing
Temperature Range
Max. Rating of Short Circuit Protective Device
Solenoid Power
Solenoid and LED Indicator Operating Voltage
Nominal Forces (Device in Unlocked State)
Insertion
Extraction
Mechanical Life
Electrical rating for gold-plated contacts
Complies with:
Machinery Directive 89/392/EEC (as amended by Directive 91/368/EEC)
EN60947-5-1 / IEC60947-5-1
MCTF (Mechanical Life): 2,587,000 cycles
MCTF (Electrical Life): 64,670 cycles
Highest SIL Capability: SIL3 (HFT:1), IEC 61508-2: 2010
Proof Test Interval: 1 Year
10
sensing.honeywell.com
24 V
120 V
--
6 A
2,8 A
0,55 A
)
imp
240 V
3 A
0,27 A
10 A
2500 V
600 V
IP68; Enclosure Type 1, 4, 6P, 12, 13
-25 °C to 40 °C (-13 °F to 104 °F)
Class J Fuse, Rating 10 A, 600 V
12 W
12 Vdc: +10 %, -20 %
24 Vdc: +10 %, -20 %
48 Vdc: +10 %, -20 %
35 N (8 lb)
28 N (6 lb)
1,000,000
10 µA to 100 mA, 1 Vac/Vdc to 50 Vac/Vdc
PK 80108
Issue 12
24 Vac: +10 %, -15 %
120 Vac: +10 %, -15 %
240 Vac: +10 %, -15 %