Faults / Solutions

Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or a bad
working of the burner.
In most cases, an operation irregularity leads to the lighting up of
the signal inside the reset button of the control box 1)(Fig. 3, on
page 11).
When lock out lamp lights the burner will attempt to light only after
pushing the reset button If ignition is then normal, the lockout can
be attributed to a temporary fault.
However, if lockout continues, you must determine the cause of
the problem and take the action illustrated in the tables below.
8.1

Start-up problems

FAULTS
The burner does not start when
the limit thermostat closes.
Burner runs normally in pre-
purging and ignition cycle and
locks out after 3 firing attempts.
Burner starts with an ignition
delay.
Faults / Solutions
POSSIBLE CAUSES
Lack of electrical supply.
Lack of gas.
The connections in the control box are
wrongly inserted.
The phase-neutral connection is inverted.
The
earth
connection
inefficient.
Valve lets too little gas through.
The gas valve is faulty.
The electric ignition arc is irregular.
The ionisation probe is earthed or not in
contact with the flame, or its wiring to the
control box is broken, or there is a fault on
its insulation to the earth.
Lack of gas.
The
ignition
electrode
positioned.
Air output is too high.
Valve brake not open enough, with
insufficient gas allowed through.
27
GB
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
ATTENTION
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
SOLUTION
Check presence of voltage in the L1-N clamps
of the 7 pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not in lockout.
Check the gate opening.
Check that valve has changed over to open
position and that there are no short circuits.
Check and connect completely all the plugs.
Invert them.
lacks
or
is
Make the earth connection efficient.
Check mains pressure and/or adjust the valve
as indicated in this manual.
Replace.
Check the right insertion of the connectors.
Check the right position of the electrode
according to the instructions of this manual.
Inspect the quality of the ceramic insulator.
Check the right position and if necessary set it
according to the instructions of this manual.
Reset the electrical wiring.
Replace the faulty connection.
Check the gate opening.
Check that valve has changed over to open
position and that there are no short circuits.
is
wrongly
Adjust it according to the instructions of this
manual.
Set the air output according to the instructions
of this manual.
Adjust it.