Fire Protection - Kemper MINI-TRESOR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EN
1
Note!
The depth (D) min. 120 mm, max. 140 mm is calculated from the
wall thickness of the outer wall including installation, clinker etc.
Note!
In order to guarantee frost protection of the water fitting, a wall
thickness (1) of 150 mm is required.
Note!
When laying the connecting pipe within the wall, a minimum wall
thickness of 285 mm is required!
Note!
The valve must be attached minimum 250 mm over the maximum
of operating water surface!
Wall opening | Recess
A wall opening must be provided with
the dimensions 325 x 285 mm (H x W).
Heat insulation against the effects of cold from outside
Heat insulation must be provided for the wall opening in consultation with
the architect! (The thickness of the insulating layer must be taken into
account accordingly for determination of the installation depth!)

Fire protection

The wall opening reduces the fire resistance duration and the structural
strength of the outer wall. A fire protection concept for the built-in wall
cabinet (1) must be produced together with the surveyor and
firesafety planner (Suggestion for an F 90 wall: Use lagging with 40 mm
Promatect H).
© www.kemper-olpe.de – 11.2021 / K410021100001-00 – 10 /32