TMT181
<
Operation
Head transmitter set-up is done using the ReadWin
ware. This is available as an accessory (see page 8).
!
Note!
When the interface cable is connected (see 'Accessories' on page 8),
the technical specifications (e.g. measured error) are not observed.
For this reason, during operation disconnect the connection via the
interface cable between the head transmitter and PC.
The following table shows the structure of the PC-Configuration
®
software ReadWin
2000 interactive menu operation:
Presettable parameters
Standard settings • Sensor type
• Connection mode (2-, 3- or 4-wire connec-
tion)
• Units (°C/°F)
• Measurement range start (depends on sen-
sor)
• Measurement range end (depends on sensor)
6
Expanded
®
2000 PC soft-
settings
Service functions • Simulation (on/off)
For detailed ReadWin
on-line documentation contained in the ReadWin
• Cold junction compensation (internal/exter-
nal on TC-connection)
• Compensation resistance (0 to 20
on 2-wire connection
• Fault condition reaction (
21.0 mA; > 21.5 mA is guaranteed)
• Output (analogue standard/inverse)
• Damping (0 to 8 s)
• Offset (-9.9 to +9.9 K)
• Measurement point identification/TAG
®
2000 operating instructions please read the

3.6 mA or
®
2000 software.