TECHNICAL DATA

Display unit
electrical device acc.
EN 60335-1
Supply voltage
Power consumption
Sound level of buzzer
Dimensions H/W/D in mm
Voltage tolerance
Housing
Ambient temperature
Type of protection
Probe
Voltage
Material
Probe length
Tank installation Probe length
Length of probe cable
Storage medium temperature
Ambient temperature
Switching and reset times
Switching
The time that the leak alarm needs to indicate the presence of stored
time
operating medium when the level increases by a specified value.
according to
Water
EN 13160-4:
Fuel oil
FAME
Reset time
The time that the leak alarm needs from displaying the stored operating
according to
medium to reach the initial status without any stored operating medium
EN 13160-4:
Water
Fuel oil
FAME

TECHNICAL CHANGES

All the information contained in this assembly and operating manual is the result of product
testing and corresponds to the level of knowledge at the time of testing and the relevant
legislation and standards at the time of issue. We reserve the right to make technical changes
without prior notice. Errors and omissions excepted. All figures are for illustration purposes
only and may differ from actual designs.
part no. 15 073 57 c
• over-voltage caterogy III
• contamination degree 2
• protection class type I
230 V AC 50 to 60 Hz
2.5 VA
≥ 70 dB(A)
120 x 120 x 50
+10 % / -15 %
Polyester
-20 °C to +60 °C
IP30 acc. to EN 60529
12 V DC
Stainless steel 1.4301
2m, 5m, 20m
maximum 1.4 m
3.6 m
-20 °C to +60 °C
-20 °C to +60 °C
10 minutes, 58 seconds
7 minutes, 49 seconds
8 minutes, 55 seconds
41 seconds
1 minute, 25 seconds
13 seconds
Leak alarm type LWG 2000