Restoration; Disposal - GOK LWG 2000 Notice De Montage Et De Service

Masquer les pouces Voir aussi pour LWG 2000:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
TROUBLESHOOTING
Fault signals during operation
Fault signal
Red LED Alarm and green LED Betrieb
(Operation) do not light up when you
connect the system.
Buzzer does not sound when the system
is connected.
Red LED Alarm is lit,
buzzer sounds.
Green LED Betrieb (Operation) is not
continuously lit.
Red LED Alarm is not lit but buzzer
sounds.
Buzzer does not sound but red LED
Alarm is lit.
Continuous alarm but no liquid on the
probe.
MAINTENANCE
Check the functions of the leak detection system regularly, but at least once per year. Check
according to FUNCTION CHECK.
It is the operator's responsibility to determine the type and frequency of the checks.

RESTORATION

If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is
no dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.
If you have a constant error message or an alarm without the probe being wet, check the
connection line between the signal part and the probe for an interruption or short circuit and
reinstall if necessary.

DISPOSAL

To protect the environment, our products may not be disposed of along with
household waste.
The product must be disposed of via a local collection station or a recycling station.
12 / 16
Leak alarm type LWG 2000
Action
Send device to the manufacturer to be checked.
Send device to the manufacturer to be checked.
The probe has responded on the display unit.
 Empty containment facility.
 Clean containment facility and probe.
 Check connected devices in the
containment facility for leaks.
Send device to the manufacturer to be checked.
Send device to the manufacturer to be checked.
Send device to the manufacturer to be checked.
Probe cable is defective.
 Check for interruption or short circuit.
Strong air flow on the probe.
 Take suitable measures to protect
probe from draughts.
part no. 15 073 57 c