Operating & maintenance
Dirt affects the operation of the detector and the detector's lens
must therefore be kept clean. Use a damp cloth for cleaning. Use
water mixed with ordinary detergent. Avoid putting pressure on
the lens. If the lens or other parts of the detector are defective, it/
they must be replaced.

Technical data

Input:
Bus voltage ..............................................30 V DC from the KNX
bus
Power consumption ...............................10 mA
Performance:
Lux range .................................................10 – 20,000 lux
Delay ........................................................1 sec. – 255 hours
Number of lighting scenes ......................8
Burn-in time .............................................10-255 hours
Sensitivity ................................................0-100 %
Light sensor hysteresis ............................0-100 %
Detection range .......................................360º, 3 x 120º
Range, body movements ........................Ø16-32 m,
(depending on installation height)
Installation height ....................................4-8 m
Enclosure class .......................................IP 54
Colour ......................................................RAL 9010 (white)
Ambient temperature ...............................-5°C to +50°C
Certifi cation:
CE pursuant to ........................................EN 60669-2-1

Accessories

IR Remote ................................................ 41-930
Quick guide
The following quick guide can be used to advantage for rapid
implementation of the motion detector.
1.
Position the sensor as shown in Fig. 1.
2.
Download the parameter database for the ETS software
from
www.servodan.dk
3.
Connect the detector to the KNX bus
4.
Enter the detector's address in the ETS software, either
using IR remote control 41-930 (accessory) or using the
programming pushbutton on the detector
5.
Select the desired application
6.
Confi gure settings with regard to light levels and delay
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com