24 V Main Power Supply / 24 V Segment Power Supply - Burkert 8644 AirLINE Instructions De Service

Masquer les pouces Voir aussi pour 8644 AirLINE:

Publicité

Les langues disponibles

Les langues disponibles

D
O
ESCRIPTION OF
VERALL

24 V main power supply / 24 V segment power supply

Connections
Connection technique
Recommended cable lengths
Forwarding
Behaviour on voltage drop and
interruption
Rated voltage
Tolerance
Ripple
Permissible range
Current loading
Min. current consumption at rated voltage
main power supply
Max. current consumption at rated voltage
main power supply
Protective features
Overvoltage
False polarity
ATTENTION!
Protect 24 V section externally!
This 24 V section must be protected externally with a fuse. The power supply unit must
be capable of supplying 4 times the rated current, so that in case of a fault, blowing of
the fuse is assured.
Terminal connection
Left
Right
Colour
1.1
2.1
black
1.2
2.2
1.3
2.3
blue
1.4
2.4
PH 6
All manuals and user guides at all-guides.com
S
B
YSTEM
ÜRKERT
Abb-
rev.
U
S
red
U
Main, bus, logic and interface supply (+24V DC)
M
GND
---
FE
- P
HOENIX
See Table TD1
Tension spring terminals
max. 30 m;
cable routing over free areas not permissible
Via potential shunting
The voltages forwarded from the bus
terminal to the potential shunters (main and
segment voltage) follow the applied supply
voltages without delay.
24 V DC
- 15 % / + 20 % (to EN 61131-2)
± 5 %
19,2 V to 30 V
Max. 8 A
0,10 A DC
(at open circuit, i.e. incoming remote bus attached, no local bus
participants connected, bus inactive)
1,25 A DC
consisting of:
0,75 A DC for logic supply
0,5 A DC for analog voltage supply
yes
yes
Meaning
Segment supply (+24V DC)
Reference potential
Functional earth
2.1
1.1
2.2
1.2
2.3
1.3
2.4
1.4
Operating Instructions No. 804 104