baltur BT 40 DSG Mode D'emploi page 34

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
10 Bottom valve
7 Return pipe
6 Suction pipe
3 Wire-net filter
4 Pump
PIPES FOR LIGHT OIL BURNER
MODEL BT 180 DSG 3V
GRAVITY SUPPLY SYSTEM
1 Tank
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
SUCTION - TYPE FEEDING SYSTEM
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
For each bend or valve deduct 0,25 m.
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
10 Feeding pipe
H
Total meters
meters
meters
Ø i. 16 mm.
1
30
1,5
35
2
35
2,5
40
3
40
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
H
Total meters
meters
meters
Ø i. 16 mm.
1
30
1,5
35
2
35
2,5
40
3
40
P = 3,5 m. (max.)
H
Total meters
meters
meters
Ø i. 16 mm.
0,5
21
1
18
1,5
15
2
11,5
2,5
8,5
3
5,5
3,5
-
N.B. For any missing devices in the piping,
follow existing regulations.
Ø i. 18 mm.
40
45
45
50
50
Ø i. 18 mm.
40
45
45
50
50
Ø i. 18 mm.
34
29
24
19
14
9
3,5
33

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bt 55 dsgBt 75 dsg-3vBt 100 dsgBt 120 dsg-3vBt 180 dsg-3v

Table des Matières