Dimmer setting:
Preset time:
Supply voltage:
E
Switch power AC1:
Output:
Electrical connections:
Material:
Entries:
Sealed against moisture and dust: IP 65 according to EN 60529
Mounting bracket:
Ambient temperature:
Housing dimensions (L x W x H):
Sensor dimensions
Weight:
6.

Marking

The occupancy sensor complies to the European Directives for EMC and ATEX and implicit
to the Low Voltage Directive. With regard to explosion safety the occupancy sensor has been
designed and manufactured on the basis of the essential health and safety requirements of
European Directive 2014/34/EU (ATEX 114) relating to Group II Category 3GD. Harmonized
European construction standards have been applied fulfilling the essential requirements of
the directives. For more details refer to section 6 Technical data and to the Declaration of
Conformity as shown on the last page of this manual.
II 3 G Ex ec mc IIC T6 Gc
II 3 D Ex mc tc IIIC T80ºC Dc
Cert. Artidor 20ATEX9999X
TF & Serial No.: AS123456
Artidor Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.Artidor.com
Example of an AR-024 occupancy sensor label
Installation manual AR-024 explosion-safe occupancy sensor
8 / 44
10 – 2,000 Lux
15 seconds – 30 minutes
230 VAC ± 10%
1,150 VA (resistive and light inductive loads)
Potential free contact
Terminals 8 x 2,5 mm²
Die cast aluminum housing (RAL 7015, slate grey),
cable glands nickel plated brass
M20 cable glands (2x) suitable for cables from 6 – 14
mm in diameter
Stainless steel mounting bracket, mounting holes Ø 6,5
(4x), distance 60 x 60 mm
-20 ˚C to +50 ˚C
120 x 120 x 195 mm (including mounting bracket,
excluding cable glands)
65 x Ø98 mm
1,860 g (incl. mounting bracket)
OCCUPANCY SENSOR
230 VAC, IP65
-20 °C < Ta < +50 °C
Type: AR-024
Year: 2020