5.

Technical Data

Explosion safety category:
Protection against ignition:
Conformity:
Standards applied:
Ambient temperature:
Material:
Dimensions magnet (L x W x H):
Mounting spacing:
Mounting:
Holding force:
Supply voltage:
Power:
Sealed against moisture and dust: IP65 according to EN 60529
Position:
Activation time:
Electrical connections:
Weight:
6.

Marking

The door magnet complies to the European Directives for EMC and ATEX and implicit to the
Low Voltage Directive. With regard to explosion safety the door magnet has been designed
and manufactured on the basis of the essential health and safety requirements of European
Directive 2014/34/EU (ATEX 114) relating to Group II Category 3GD. Harmonized European
construction standards have been applied fulfilling the essential requirements of the
directives. For more details refer to section 5 "Technical data" and to the EU Declaration of
Conformity as shown on the last page of this manual.
Installation manual explosion-safe AR-030 door magnet
II 3GD
Ex ic mc IIC T6 Gc, Ex ic mc IIIC T80ºC Dc
2014/34/EU (ATEX 114) and 2014/30/EU (EMC)
EN 60079-0:2018, EN 60079-11:2012 and
EN 60079-18:2015 / A1:2017
-25 ºC to +50 ºC
Impact-resistant plastic housing and nickel plated
magnet
Ø 50 mm
Floor / ceiling mounting: 150 mm, wall mounting:
175 mm
Ø 4.5 mm mounting holes (4x), mutual distance 55 x
55 mm
490 N
24 V AC/DC ± 10%
100 mA AC / 63 mA DC
Adjustable (360º)
100%
Cable, numbered, 3 x 1 mm², length 5 meters
770 grams
E
12-2022