Lockouts
In case of a lockout, a warning triangle (E) and a flashing error code appears on the display. The cause of a fault should first
be determined and eliminated before the boiler is being reset. In case the lockout appears more than twice within 6 minutes or
maintains for longer than 6 minutes, the error code is added with a "
indication of possible cause.
No. Error type Explanation
1
Lockout
Water flow temperature has exceeded the high
limit temperature setting (100ºC).
Interlock
Gas pressure has dropped below minimum value
2
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during startup).
3
Interlock
Gas pressure has dropped below minimum value
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during operation).
4
Lockout
No flame ionisation signal detected during burner
start.
Lockout
Flame ionisation signal lost during operation.
5
Interlock
Water flow temperature has exceeded the
6
temperature limiter setting (97ºC).
7
Lockout
Fluegas temperature has exceeded the high limit
temperature setting (100ºC).
11
Lockout
Flame ionisation signal detected before burner
start.
12
Interlock
Water flow temperature sensor is defective
13
Interlock
Fluegas temperature sensor is defective
Interlock
DHW temperature sensor (optional) is defective
14
15
Interlock
Outside temperature sensor (optional) is
defective
Interlock
Header temperature sensor (optional) is defective Check resistance of sensor (see chapter "sensor va-
18
3
". The table below shows all possible lockouts and an
Possible solution
Check if boiler is in automatic mode (K), Check if water
flow through the boiler is sufficient, check if (P11+P12)
< High limit setting (V9).
Check gas supply pressure / check function of
additional safety device on interlock input.
Check gas supply pressure / check function of
additional safety device on interlock input.
Check phase/neutral of power supply (phase
sensitivity!), check gas supply, check ignition spark,
increase gas valve setting min. load (alan key screw).
Check gas supply pressure during operation, check
gas valve setting via combustion analysis.
Check if boiler is in automatic mode (F), check if water
flow through the boiler is sufficient, check if (P11+P12)
< Temp. limiter setting (V10).
Check if water pressure is sufficient, check if water
flow through the boiler is sufficient, check if heat
exchanger is clean (fluegas and water side).
Check ionisation electrode, measure ionisation current
when boiler is off, check wiring between ionisation
electrode and boiler controller.
Check resistance of sensor (see chapter "sensor va-
lues"), check wiring between water flow temperature
sensor and boiler controller.
Check resistance of sensor (see chapter "sensor va-
lues"), check wiring between fluegas temperature sen-
sor and boiler controller.
Check resistance of sensor (see chapter "sensor va-
lues"), check wiring between DHW temperature sensor
and boiler controller.
Check resistance of sensor (see chapter "sensor va-
lues"), check wiring between outside temperature sen-
sor and boiler controller.
lues"), check wiring between header temperature sen-
sor and boiler controller.
25