Eaton Pulsar Serie Mode D'emploi page 21

Masquer les pouces Voir aussi pour Pulsar Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
Output personalisation
Function
Factory setting
(1)
Output voltage
230 Volts AC
(1)
Frequency converter
Disabled
(1)
Output frequency
Automatic selection
Transfer to the bypass
Bypass AC power must
(1)
AC input
be within tolerances
(1)
Overload level
100%
(1) These parameters may be modified only when the UPS is OFF.
ON/OFF personalisation
Fonction
Personnalisation usine
Start on battery power
Enabled
Automatic restart
Enabled
Energy savings
Disabled
Detection of phase/
Disabled
neutral inversion (SWF)
Battery personalisation
Function
Factory setting
Battery test
Weekly test
Low-battery warning
20%
Selection of the backup
Automatic detection of
time
number of battery
modules
Battery protection
Enabled
against excessive
discharges
Other available settings
Comments
200/208/220/240/250 Volts
AC
Enabled
The connected devices are never
transferred to the bypass.
50 or 60 Hz
User selectable only if the
frequency-converter function is
enabled.
Bypass AC power may be
outside tolerances
30 / 50 / 70%
Alarm if threshold is overrun.
Autres choix
Commentaires
Disabled
Disabled
The UPS restarts automatically
when AC power returns.
Enabled
When function enabled, battery
shuts down when power drops to
<5%.
Enabled
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
Other available settings
Comments
No test / daily test /
monthly test
0 to 100%
Adjustable in 1% steps.
13 to 200 Ah
Disabled
When function disabled, EATON
warranty no longer applies.
- Page 19
34008097EN/AE

Publicité

Table des Matières
loading

Table des Matières