TRI-LITE HVLS SERIES FANS
ELECTRICAL SAFETY
WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
ELECTRICAL HAZARD
WARNING! Only qualified electricians are allowed to install the drive and connections to the motor!
!
Never work on the drive, motor cable or motor when input power is applied. After disconnecting the input power, always wait
for 5 minutes to let the intermediate circuit capacitors discharge before you start working on the drive, motor or motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm) that
1. There is no voltage between the drive input phases U1, V1 and W1 and the ground.
2. There is no voltage between terminals BRK+ and BRK- and the ground.
Do not work on the control cables when power is applied to the drive or to the external control circuits. Externally supplied
control circuits may carry dangerous voltage even when the input power of the drive is switched off.
GENERAL SAFETY
!
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
• Installation work and electrical work must be done by qualified person(s) in accordance with all applicable codes and
standards, including fire-rated construction.
• The installation is to be in accordance with the National Electrical Code, CSA C22.1, ANSI/NFPA 70, and local codes.
TOOLS REQUIRED TO INSTALL PRODUCT
• Level
• Cable cutters (for stainless steel aircraft cable)
• Ratchet or impact gun
• Basic imperial socket set up to 7/8" will fit bolt heads and nuts
• Basic imperial wrench set up to 7/8" will fit bolt heads and nuts
• Lifting device or scaffolding
REQUIRED STEPS BEFORE INSTALLATION
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
!
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
• The Tri-Lite HVLS fan must be installed with the proper length of blades
to match the VFD that are marked to indicate their suitability with this
model.
• No other blades or VFD can be substituted.
• Check to see if you have all of the tools required for the installation.
• Verify that all fan components were received.
• Check drawings and layouts provided to locate where the Tri-Lite HVLS  Fan is to be installed.
• Ensure work area is safe and that all security, policies and procedures for the facility are met.
• Inspect the lift device or mobile platform.
• Each person installing the Tri-Lite HVLS  Fan must use a safety harness at all times.
• Other safety requirements may be required for installation.
• All workspace safety requirements, lock out procedures and hoarding of construction zone for the assembly
and installation must be met and followed.
TRI-LITE HVLS-M (04_29_15)
CAUTION
THIS UNIT HAS AN UNGUARDED IMPELLER.
DO NOT USE IN LOCATIONS READILY
ACCESSIBLE TO PEOPLE OR ANIMALS.
TO REDUCE THE RISK OF INJURY TO PERSONS,
INSTALL FAN SO THAT THE BLADE IS AT LEAST
10 FEET ABOVE THE FLOOR.
WARNING
SUPPORT DIRECTLY FROM BUILDING STRUCTURE
CAUTION
MOUNT WITH THE LOWEST MOVING PARTS
AT LEAST 10 FEET ABOVE FLOOR OR GRADE LEVEL.
Page 2 of 13