TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7, DL8, DL9 and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following and replace any faulty components.
DL6
OFF
Stop button malfunction (if Stop is not connected, perform the jump between COM A+ and STOP).
DL7 or DL8
OFF
Faulty photocells (In case the edge is not connected, carry out jumper between COM A+ and PHOTO 1/PHOTO 2)
DL9 or DL10
OFF
Faulty safety edge (In case the edge is not connected, carry out jumper between COM A+ and EDGE 1/EDGE 2)
During functioning with personnel present, with DIP 1 at ON, check that during opening of M1 and M2 the green DL2 and DL4 LEDS switch on and that during closing of M1 and M2 the red DL3 and
DL5 LEDS switch on.
Or else, reverse the wires of the motor.
DL13 blue
ON
Some functions are enabled via smartphone, so via smartphone check the card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit, interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and insert them one at a time in order to more easily identify the cause of the fault.
After having carried out the various connections and having supplied voltage, all the LEDS are
switched OFF.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various START, RADIO, OPEN and CLOSE
buttons.
The electric lock does not work.
Impact sensor intervenes during the movement
The buzzer emits 2 long tones and the gate does not move
The remote control does not work. Led DL12 lit red
FAULT
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and
insert them one at a time in order to more easily identify the cause of the fault.
Check fuses F1, F2.
If the fuse is blown, use only a suitable replacement.
F1 T 2A
TRANSFORMER PROTECTION FUSE (on the outside of the B2 24V board)
F2 T 8A
MOTOR PROTECTION FUSE
Check trimmers RUN and LOW SP adjustment.
Make sure that the TCA trimmer is activated with LED DL11 ON.
B.I.O. contact always on => check the status of the clock connected to B.I.O..
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
Stop, Edge or Photocell with DIP 4 OFF contact fault => Fix or replace the faulty contact.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
Ensure to have enabled DIP 8 at ON.
Check the cable.
Turn the SENS trimmer clockwise
Safety edge with 8,2 KΩ resistor. Remove the resistor or configure the EDGE input via the RIB
GATE app
Lack of radio module in connector J6 or faulty radio module.