Auto Test (Vo/c Is/c & insulation resistance)
1.
Connect the EazyPV to the PV module
as shown, using the PV testlead adaptors
2.
Vo/c is automatically displayed
3.
If the voltage polarity is incorrect the
reversed polarity icon will appear on the
LCD. The auto test sequence is inhibited if
the polarity is reversed
4.
Use the
button to select 250 V, 500 V
or 1000 V insulation test voltage
5.
Press the
button to automatically
measure short circuit current and insulation
resistance
Note:
The red test probe is required for the insulation
resistance measurement
AC&DC current measurement
(optional current clamp required)
1.
Disconnect all cables from the EazyPV
test inputs
2.
Connect the current clamp to the red &
black 4 mm inputs
3.
Move the current clamp switch to the 40 A
position
4.
Zero clamp according the manual of the
clamp
5.
Press the
button; the clamp icon will
appear on the LCD
6.
The measured current is shown on the LCD
www.nieaf-smitt.com