Testlead resistance null
1.
Connect testleads to red and black 4 mm
sockets on the EazyPV
2.
Hold the test probe tips together or
connect together using the supplied
alligator clips
3.
Press and hold the
beeps and NULL icon appears on LCD
4.
Null value is stored when unit is switched
off
5.
To disable, press
key until icon is
removed from LCD
Note:
Maximum testlead resistance null is 10 Ω
www.nieaf-smitt.com
24

Protective earth resistance

1.
2.
3.
key until the unit
4.
Connect the testleads a shown
To make a 2 s measurement, press and
release the
key
To make a continuous measurement, press
and hold the
key for a few seconds
until the lock icon appears on the LCD
Press the
key to terminate the
continuous measurement mode