Radio Configuration - Xylem PolluStat Instructions De Montage Et Manuel D'utilisation

Compteur d'énergie thermique à ultrasons
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1.3 Radio interface wireless M-Bus EN 13757-3, -4 (optional)
The radio interface is for the transmission of meter data (absolute values).
General information about the radio interface:
Installation of radio components between or behind heating pipes, or the presence of other
bulky metallic obstacles directly over or in front of the housing must be avoided.
The transmission quality (range, telegram processing) of radio components can be negatively
influenced by instruments or equipment with electromagnetic emissions, such as telephones
(particularly LTE mobile radio standard), wi-fi routers, baby monitors, remote control units,
electric motors, etc.
In addition, the construction of the building has a strong influence on the transmission range
and coverage. Furthermore, when using installation boxes (substations) they must be
equipped with non-metallic covers or doors.
The factory-setting of the clock in the meter is standard (winter) Central European Time (GMT +1). There is no automatic
changeover to daylight savings (summer) time.
The radio function is deactivated upon delivery (factory-setting). See section "Activation of the radio interface".
1.3.1 Technical data radio
Frequency
Transmission power
Protocol
Selectable modes
Telegrams
Encryption

1.3.2 Radio configuration

Parameter
Mode
Transmission period
Transmission interval
Weekdays
Weeks in a month
Months
Radio activation date
AES-128-Encryption
Type of telegram
Page 98 of 108
Article no.: 1080619046
868 MHz
up to 12 dBm
wireless M-Bus based on EN 13757-3, -4
S1 / T1 / C1
-
short telegram in conformity to AMR (OMS-Spec_Vol2_Primary_v301 and _v402):
energy (heat/cooling energy, pulse input 1 to pulse input 3), total volume, flow, power,
information message, outlet flow temperature, temperature difference
-
long telegram for walk-by read-out: energy (heat/cooling energy, pulse input 1 to pulse
input 3), total volume, information message, 15 monthly or 30 semimonthly values
(compact mode)
AES: Advanced Encryption Standard; key length: 128 bits
Possible settings
S1 / T1 / C1; unidirectional
00:00 - 24:00; any time period in the day
10 seconds - 240 minutes
Monday – Sunday (any weekday)
1 – 4 (4: uninterrupted, incl. a possible 5
week)
1 - 12
01.01. - 31.12. (day. month)
-
not encrypted;
- encrypted according to MODE 5 or
MODE 7:
-
Master Key
-
key per instrument
-
short telegram in conformity to AMR
(OMS-Spec_Vol2_Primary_v301 and
_v402)
-
long telegram for walk-by read-out
Factory setting
(Battery lifetime, estimated: 10 years)
T1 (unidirectional)
8:00 am - 6:00 pm
120 seconds (heat meters)
Monday - Friday
th
1 – 4 (4: uninterrupted)
1 - 12
not set
Master Key; not activated
short telegram (AMR)
2020_07_27
Subject to technical change! Errors excepted.