1.5.2 Technical data for one pulse output and two pulse outputs
Pulse outputs class
Connecting cable length
Switching voltage, maximum
Switching current, maximum
Contact resistance (on) max.
Contact resistance (off) min.
Closure time
Interval between pulses
1.6 Two potential-free pulse outputs (optional)
The potential-free pulse outputs provide counting pulses of the meter.
The pulse outputs close corresponding to the pulse value, see items „pulse value pulse output
1" and „pulse value pulse output 2" in display loop "6" (module loop).
Heat meter
Pulse output 1
heat energy
Pulse output 2
volume
Pulse outputs for energy:
The pulse value for energy is always determined by the last place of the energy display.
Examples:
Display: 0 kWh
Display: 0,000 MWh
0,000 GJ -> pulse value: 0,001 GJ/pulse
Pulse outputs for volume:
The pulse value for volume is always determined by the second-to-last place of the volume display.
Example:
Display: 0,000 m³ -> pulse value: 10 l/pulse (0,01 m³/pulse)
1.6.1 Pin assignments 4-wire cable
Color
Yellow
Green
Brown
White
2 Retrofitting with an Additional Communication Interface
During installation of the retrofitting module observe the ESD requirements according to EN 61340-5-1.
This means that on location an antistatic wrist strap with an integrated 1 MΩ resistor has to be used which must be connected
to a proper spot: This is either a grounded pipe or – only with an appropriate adapter! – a Schuko plug grounding socket. The
antistatic wrist strap must be worn tightly on the skin of the wrist.
2.1 Retrofitting PolluStat with an additional communication interface (optional)
We also offer a retrofittable meter to which communication interfaces can be added later.
Page 102 of 108
OA (electronic switch) according to EN 1434-2:2016
1 m
30 V
27 mA
74 Ω
6 MΩ
100 ms
100 ms
Cooling meter
cooling energy
volume
-> pulse value: 1 kWh/pulse
-> pulse value: 0,001 MWh/pulse Display:
Connection
IA1
IA1
IA2
IA2
Article no.: 1080619046
Heat/cooling meter
heat energy
cooling energy
2020_07_27
Subject to technical change! Errors excepted.