10. PARAMETERS

Hy Intervention differential for set point: (0.1 to 12.0 res. 0.1°C or 1°F) always positive. Compressor cut-
IN is SET+HY. Compressor cut-OUT is when the temperature reaches the set point.
AC Anti-short cycle delay: (0 to 30 min) minimum interval between the compressor stop and the following
restart.
PAU Time of stand by: (0 to 60 min) after this time the controller restart the cycle.
PFt Maximum acceptable duration of power failure: (0 to 250 min) if power failure duration is less than
PFt, the cycle restarts from the same point at which it was stopped otherwise the cycle restarts from the
beginning of the current phase.
Con Compressor ON time with faulty probe: (0 to 255 min) time during which the compressor is active in
case of faulty thermostat probe. With COn=0 compressor is always OFF.
CoF Compressor OFF time with faulty probe: (0 to 255 min) time during which the compressor is off in
case of faulty thermostat probe. With CoF=0 compressor is always active.
rPOThermostat probe calibration: (-12.0 to 12.0, res. 0.1°C or 1°F).
EPP Evaporator probe presence (not present in the XB350C): (no / YES) no: not present (timed defrost);
YES: present (end defrost).
EPO Evaporator probe calibration (not present in the XB350C): (-12.0 to 12.0, res. 0.1°C or 1°F).
i1P Insert probe 1 presence: (no / YES) no: not present; YES: present.
i1o Insert probe 1 calibration: (-12.0 to 12.0, res. 0.1°C or 1°F).
i2P Insert probe 2 presence: (no / YES) no: not present; YES: present.
i2o Insert probe 2 calibration: (-12.0 to 12.0, res. 0.1°C or 1°F).
i3P Insert probe 3 presence: (no / YES) no: not present; YES: present.
i3o Insert probe 3 calibration: (-12.0 to 12.0, res. 0.1°C or 1°F).
rEM End cycle probe selection: (iPt; rP) it sets which probe stops teh the cycle, thermostat probe or insert
probe:
iPt=insert probe;
rPt=thermostat probe.
NOTE: with rEM = rPt when the cycles are done by temperature, the rSi values are used as stop
of the cycle.
CF Temperature measurement unit: °C=Celsius; °F=Fahrenheit.
rES Resolution (for °C): in=integer; de=with decimal point.
Lod Upper display visualization: select which probe isshown by the upper display:
rP=Thermostat probe
EP=Evaporator probe
rEd Remote display, X-REP, visualization: select which probe is displayed by the X-REP:
rP=Thermostat probe; EP=Evaporator probe; tiM=cycle count down; i1P=insert probe 1; i2P=insert
probe 2; i3P=insert probe 3.
d1P Door switch input polarity (25-26): (OP; CL) select if the digital input is activated by opening or closing
the contact. OP= opening; CL=closing.
odC Compressor and fan status when open door:
no=normal;
FAn=Fan OFF;
CPr=Compressor(s) OFF;
F_C=Compressor(s) and fan OFF.
doA Open door alarm delay: (0 to 254min, 255=nu) delay between the detection of the open door condition
and its alarm signalling: the flashing message "dA" is displayed. If doA=nu the door alarm will be not
signalled.
dLc Stop count down of the running cycle with door open: Y=count down is stopped with door opening;
n=count down goes on with door open.
1592006207 XB570L GB r1.1 26.08.2015
REGULATION
PROBES
DISPLAY AND MEASUREMENT UNIT

DIGITAL INPUTS