Mounting Decoration Panel - Daikin FXFQ07TVJU Manuel D'installation

Masquer les pouces Voir aussi pour FXFQ07TVJU:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7-6 FOR CONTROL WITH 2 REMOTE CONTROL-
LERS (TO CONTROL 1 INDOOR UNIT WITH 2
REMOTE CONTROLLERS)
• For control with 2 remote controllers, set one remote con-
troller as Main and the other remote controller as Sub.
< Changeover method from Main to Sub and vice versa >
Refer to the installation manual attached to the remote
controller.
< Wiring method >
(1) Remove the control box lid.
(2) Carry out additional wiring from the remote controller
2 (Sub) to the terminals (P1, P2) for remote controller
wiring on the terminal block (X1M) in the control box.
P1
P2
F1
F2
T1
Remote
Remote
controller 2
controller 1
(Sub)
(Main)
< Caution >
• When using the group control and the 2 remote control-
lers control at the same time, connect the remote con-
troller 2 (Sub) to the indoor unit at the end of the cross-
over wiring (the largest No.). (Refer to Fig. 29)
Indoor unit 1
Indoor unit 2
Remote
Crossover
controller 1
wiring (Remote
(Main)
controller)
Fig. 29
7-7 FOR CENTRALIZED CONTROL
• When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on
the remote controller.
For details, refer to the manuals attached to the centralized
equipment.
• Connect the centralized equipment to the indoor unit con-
nected to the remote controller.
7-8 FOR REMOTE CONTROL (FORCE OFF OR ON /
OFF OPERATION)
(1) Wiring method and specification
• Remote control is available by connecting the external
input to the terminal T1 and T2 on the terminal block for
remote controller and transmission wiring (X1M).
15
T2
Terminal block
(X1M)
Terminal for remote
controller wiring (P1, P2)
No polarity
Indoor unit
largest No.
Remote
controller 2
(Sub)
F2
T1
T2
FORCED
OFF
Input A
(2) Actuation
• Input A of FORCED OFF and ON/OFF OPERATION
will be as the table shown below.
Input A = ON
In case of FORCED
Remote controller
OFF
prohibited
In case of ON/OFF
Operation
OPERATION
(3) How to choose FORCED OFF or ON/OFF OPERA-
TION
• For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to 9. FIELD SETTING AND TEST OPERATION.)

8. MOUNTING DECORATION PANEL

<<If test operation is required before mounting the deco-
ration panel, 9. FIELD SETTING AND TEST OPERATION
can be carried out before 8. MOUNTING DECORATION
PANEL.>>
CAUTION
In case of a wireless remote controller, unless the decoration
panel is mounted, field setting and test opera tion cannot be
carried out.
Refer to the installation manual attached to the decoration
panel.
• After the decoration panel is mounted, check if no clear-
ance exists between the panel and the unit.
• If test operation is carried out before mounting the decora-
tion panel, check the swing blade action after the panel is
mounted.
Sheathed vinyl
Wiring
cord or 2 core
specification
cable
AWG18-16
Gauge
(0.75 – 1.25 mm
Max. 328 ft.
Wiring length
(100 m)
Contact that can
External
make and break
contact spec
the min. load of
15 V DC , 1 mA
Input A = OFF
Remote controller
permitted
Stop
3P161684-7N
English
)
2

Publicité

Table des Matières
loading

Table des Matières