Daikin FXFQ07TVJU Manuel D'installation page 15

Masquer les pouces Voir aussi pour FXFQ07TVJU:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7-3 SPECIFICATION FOR FIELD SUPPLY FUSES
AND WIRING
Power supply wiring
MOP
Size
Wiring size and
length must
15A
comply with local
codes.
The lengths of remote controller wiring and transmission wir-
ings are as follows:
(1) Remote controller wiring (indoor unit - remote controller)
..................................................................Max. 1,640 ft. (500 m)
(2) Transmission wirings ... Total wiring length 6,560 ft. (2,000 m)
• Outdoor unit - Indoor unit ........ Max. 3,280 ft. (1,000 m)
• Outdoor unit - BS unit ............. Max. 3,280 ft. (1,000 m)
• BS unit - Indoor unit ................ Max. 3,280 ft. (1,000 m)
• Indoor unit - Indoor unit .......... Max. 3,280 ft. (1,000 m)
NOTE
1. Shows only in case of protected piping. Use H07RN-F in
case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness :
0.04 in. (1 mm) or more)
7-4 WIRING CONNECTION METHOD
CAUTION FOR WIRING
• The indoor units in the same system can be connected to
the power supply from one branch switch. How ever, selec-
tion of branch switch, branch over current circuit breaker
and wiring size must be according to applicable legislation.
• For connection to the terminal block, use a ring type crimp
style terminals with insulation sleeve or insulate the wirings
properly.
Insulation sleeve
Ring type crimp
style terminals
• If the above is not available, make sure to fulfill the following
requirements.
Connection of 2
Connection of 2
wirings of same
wirings on one
size must be
side is
carried out on
prohibited.
both sides.
(Abnormal heating may occur if the wirings are not tight-
ened securely.)
• Use the required wirings, connect them securely and fix
these wirings securely so that external force may not apply
to the terminals.
• Use a proper screw driver for tightening the terminal
screws.
If an improper screw driver is used, it may damage the
screw head and a proper tightening cannot be car ried out.
3P161684-7N
English
Remote controller wiring
Transmission wiring
Wiring
Size
Vinyl cord with
AWG
sheath or cable
18-16
(2 core)
Wiring
Connection of
wirings of
different sizes is
prohibited.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
terminals.
Terminal block for remote controller
and transmission wirings
Terminal for power supply
Ground terminal
• Do not carry out soldering finish when stranded wirings
are used.
WARNING
• When wiring, form the wirings orderly so that the control
box lid can be securely fastened. If the control box lid is not
in place, the wirings may float up or be sandwiched by the
box and the lid and cause electric shocks or a fire.
< Power supply wiring · ground wiring · remote controller
wiring · transmission wiring connecting method >
• Power supply wiring, ground wiring
Pass the power supply wire through the attached insula-
tion tube (16) between the outlet of conduit and the power
supply terminal, and bind them together with the attached
clamp (4). (Refer to Fig. 23-2)
Use a pair of conduit mounting plates (17) to connect a
conduit to the unit as shown Fig. 23-1. After connecting the
power supply wiring to [L
· L
1
block (X2M) and the ground wiring to the ground terminal,
clamp them near the terminal block using the attached
clamp (4). (Refer to Fig. 23-2)
Remote controller wiring, transmission wiring
Pull the wiring through the wiring penetrating hole (low volt-
age). After connecting the remote controller wir ing to [P1 ·
P2] and the transmission wiring to [F1 · F2] on the terminal
block (X1M), clamp them near the terminal block using the
attached clamp (4). (Refer to Fig. 23-2)
• After connecting the wiring, make sure to stick the sealing
material (Small) (13) to the wiring penetrating hole to pre-
vent water from entering the indoor unit. (Refer to Fig. 24)
CAUTION
• Never connect the power supply wiring to the terminal
block for remote controller/transmission wiring (X1M).
If may damage the total system.
• Do not connect the remote controller/transmission wir-
ing to the wrong terminal block.
Tightening torque
[lbf·ft. (N·m)]
0.65 ± 0.07
(0.88 ± 0.08)
0.965 ± 0.095
(1.31 ± 0.13)
] on the power supply terminal
2
12

Publicité

Table des Matières
loading

Table des Matières