Example:
-
AC input current limitation on the leader and the followers: 12A
-
If the charging current on the leader is set to 100% (70A for a Multi
24/3000/70) and the system consists of three devices, then the effective
system charging current is equal to 3 x 70 = 210A.
The settings according to this example (9kVA 3-phase system without Multi Control
Panel) are as follows:
Leader (L1)
DS-8 AC input
12A
DS-7 AC input
12A
DS-6 AC input
12A
DS-5 AES
na
DS-4 Ch. current
3x70A
DS-3 Ch. current
3x70A
DS-2 Leader
DS-1 Leader
To store the settings after the required values have been set: press the 'Up' button of
the leader for 2 seconds (upper button to the right of the DIP switches, see appendix
A, position K). The overload and low-battery LED's will flash to indicate
acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe
place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
30
off
DS-8 AC in 12A
on
DS-7 AC in 12A
on
DS-6 AC in 12A
DS-5 na
on
DS-4 na
DS-3 na
on
DS-2 Slave 1
DS-1 Slave 1
on
off
Follower (L2)
off
on
on
off
off
Follower (L3)
DS-8 AC in 12A
DS-7 AC in 12A
on
DS-6 AC in 12A
on
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
DS-1 Slave 2
on
off
off