5. Configuration

Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings
are suitable for single-unit operation.
Warning:
Possibly, the standard battery charging voltage is not suitable for
your batteries! Refer to the manufacturer's documentation, or to
your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on/ off
Charging characteristics
BatterySafe mode
Charging current
current
Battery type
Automatic equalisation charging
Absorption voltage
Absorption time
time)
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
AC input current limit
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
18
50 Hz
45 - 65 Hz
180 - 265 VAC
230 VAC
stand-alone
off
on
on
four-stage adaptive with
75% of the maximum charging
Victron Gel Deep Discharge (also
suitable for Victron AGM Deep
Discharge)
off
14.4 / 28.8 / 57.6 V
up to 8 hours (depending on bulk
13.8 / 27.6 / 55.2 V
13.2V (not adjustable)
1 hour
7 days
on
30A or 16A depending on model
(current limit for PowerControl and
PowerAssist functions)
on
off
off
2