Guidance and Manufacturer's Declaration

Guidance and Manufacturer's Declaration—Electromagnetic Emissions
This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The customer
or the user of this Medical-Grade UPS should assure that it is used in such an environment.
Emissions Test
RF Emissions CISPR 11
RF Emissions CISPR 11
Guidance and Manufacturer's Declaration—Electromagnetic Immunity
This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The customer
or the user of this Medical-Grade UPS should assure that it is used in such an environment.
Immunity Test
Electrostatic Discharge (ESD)
IEC 61000-4-2
Electrical Fast Transient/Burst
IEC 61000-4-3
Surge
IEC 61000-4-5
Voltage dips, short
interruptions and voltage
variations on power supply
input lines
IEC 61000-4-11
Power Frequency (50/60 Hz)
Magnetic Field
IEC 61000-4-B
Note: U T is the AC mains voltage prior to application of the test level.
15-08-266-9333A2.indb 14
Compliance Electromagnetic Environment - Guidance
Group 1
The Medical-Grade UPS uses RF energy only for its internal
function. Therefore, its RF emissions are very low and unlikely to
cause any interference in nearby electronic equipment.
Class B
The Medical-Grade UPS is suitable for use in all establishments
other than domestic and those directly connected to the public
low-voltage power supply network that supplies buildings used for
domestic purposes.
IEC 60601 Test Level
+ / - 6kV contact
+ / - 8kV air
+ / - 2kV for power supply lines
+ / - 1kV for input/output lines
+ / - 1kV differential mode
+ / - 2kV common mode
<5% U T
(>95% dip in U T ) for .5 cycle
40% U T
(60% dip in U T ) for 5 cycles
70% U T
(30% dip in U T ) for 25 cycles
<5% U T
(>95% dip in U T ) for 5 seconds
3 A/m
14
Compliance
Electromagnetic
Level
Environment - Guidance
Complies
Floors should be wood,
concrete or ceramic tile.
If colors are covered with
synthetic material, the relative
humidity should be at least
30%.
Complies
Mains power quality should be
that of a typical commercial or
hospital environment.
Complies
Mains power quality should be
that of a typical commercial or
hospital environment.
Complies
Mains power quality should be
that of a typical commercial or
hospital environment.
Complies
Power frequency magnetic
fields should be at levels
characteristic of a typical
location in a typical commercial
or hospital environment.