Checks After Adding Refrigerant; Before Operation; Service Precautions - Panasonic URBAN MULTI U-8ME4XPQ Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 55
4
The weighed and already recorded amount of additional
refrigerant charge (not the total amount of refrigerant present in
the system) must be entered by selecting the corresponding
LED display.
Scroll through the possible LED combinations by pressing the
button until the LED combination corresponds to the
BS2 SET
weight of additional refrigerant charge you must input.
Select the required input by pressing the
and confirm the input into the PCB by pressing the
button again.
BS3 RETURN
Possible LED combinations in function of weight of additional
refrigerant charge (= x) to input;
kg
H1P H2P H3P H4P H5P H6P H7P
w x x x x x x
0
x=0
w x x x x x w
1
0<x<5
w x x x x w x
2
5≤x<10
w x x x x w w
3
10≤x<15
w x x x w x x
4
15≤x<20
w x x x w x w
5
20≤x<25
w x x x w w x
6
25≤x<30
w x x x w w w
7
30≤x<35
w x x w x x x
8
35≤x<40
w x x w x x w
9
40≤x<45
w x x w x w x
10
45≤x<50
w x x w x w w
11
50≤x<55
w x x w w x x
12
55≤x<60
w x x w w x w
13
60≤x<65
w x x w w w x
14
65≤x<70
w x x w w w w
15
70≤x<75
w x w x x x x
16
75≤x<80
w x w x x x w
17
80≤x<85
w x w x x w x
18
85≤x<90
w x w x x w w
19
90≤x<95
w x w x w x x
20
95≤x<100
w x w x w x w
21
100≤x
5
Return to setting mode 1 (= initial state) by pressing the
button.
BS1 MODE
If you get confused in the middle of the input
NOTE
process, press the
setting mode 1 (= initial state).
The H1P LED is off
Resume the input procedure from step 2 onwards.
Perform a test operation as described in "12.4. Test operation" on
page 23.

11.7. Checks after adding refrigerant

Are the stop valves for both liquid and gas open?
Is the amount of refrigerant, that has been added, recorded on
the refrigerant charge label?
Make sure to open the stop valves after charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
Installation manual
20
button
BS3 RETURN
button to return to
BS1 MODE
x
.
12. B
EFORE OPERATION
12.1.

Service precautions

WARNING: ELECTRIC SHOCK
Caution
when
performing
equipment
1
Do not open the electric component box cover for 10
minutes after the power supply is turned off.
2
Measure the voltage between terminals on the
terminal block for power supply with a tester and
confirm that the power supply is shut off.
In addition, measure the points, as shown in the figure
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC.
A2P
A2P
TP1 TP2
3
To prevent damaging the PC-board, touch a non-coated
metal part to eliminate static electricity before pulling out
or plugging in connectors.
4
Pull out junction connectors X1A, X2A, X3A, X4A
(X3A and X4A of REYQ14+16P are inside the electric
component box (2), refer to the wiring diagram) for the
fan motors in the outdoor unit before starting service
operation on the inverter equipment. Be careful not to
touch the live parts.
(If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and
cause electric shock.)
5
After the service is finished, plug the junction
connecter back in. Otherwise the error code E7 will be
displayed on the remote controller and normal
operation will not be performed.
For details refer to the wiring diagram labelled on the back
of the electric component box cover.
Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Be sure to turn off the main switch and to remove the
fuses from the control circuit located in the outdoor unit.
NOTE
Play it safe!
For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your
body before performing service.
service
to
inverter
A1P
A3P
U-8~16ME4XPQ
Urban Multi air conditioner
4PW40726-1A

Publicité

Table des Matières
loading

Table des Matières