Normal Operation / Flame Sensor Timing - Riello RX 350S/P Manuel D'entretien

Table des Matières

Publicité

Signal
The burner does not switch
10 x blinks
on, and the lockout appears
The burner goes to lock-out
No blink
The burner does not start
The burner repeats the start-
ing cycle without lock out
Ignition with pulsations
Burner does not reach maxi-
mum output
Burner stops with air gate
valve open

NORMAL OPERATION / FLAME SENSOR TIMING

The control box has a further function by means of which it is possible to check the correct running of the burner (signal: GREEN LED permanently lit up).
In order to use this function, it is necessary to wait at least ten seconds from the firing up of the burner and press the button of the control box for a mini-
mum of three seconds.
Once the button has been released, the GREEN LED will start to flash, as illustrated in the diagram below.
GREEN LED on
wait at least 10 secs
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will identify the SENSOR TIMING o f the probe from opening of the gas valve, according to the table below.
SIGNAL
1 flash
2 flashes
6 flashes
KIT INTERFACE ADAPTER RMG TO PC Code 3002719
Problem
37 - Incorrect electrical wiring. . . . . . . . . . . . . . . . . . . . . . . . . Check
38 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
39 - Presence of electromagnetic disturbance . . . . . . . . . . . . Use the radio disturbance protection kit
40 - No electrical power supply . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections
41 - A limiter or safety control device is open. . . . . . . . . . . . . Adjust or replace
42 - Line fuse blocked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
43 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
44 - No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between contactor and train
45 - Mains gas pressure insufficient. . . . . . . . . . . . . . . . . . . . Contact your GAS COMPANY
46 - Minimum gas pressure switch fails to close . . . . . . . . . . Adjust or replace
47 - Servomotor fails to move to min. ignition position
48 - The gas pressure in the gas mains lies very close to the
value to which the gas pressure switch has been set.
The sudden drop in pressure after valve opening causes
temporary opening of the pressure switch itself, the
valve immediately closes and the burner comes to a halt
49 - Poorly adjusted head . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust. See page 7
50 - Ignition electrode incorrectly adjusted. . . . . . . . . . . . . . . Adjust it, see fig. (D) page 6
51 - Incorrectly adjusted fan air damper: too much air . . . . . . Adjust
52 - Output during ignition phase is too high . . . . . . . . . . . . . Reduce
53 - Remote control device TR fails to close . . . . . . . . . . . . . Adjust or replace
54 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
55 - Defective servomotor . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
56 - Defective servomotor . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Press button
for > 3 secs
FLAME SENSOR TIMING
0.4 secs
0.8 secs
2.8 secs
Possible cause
Signal
Each time the burner is started up, this information is up-dated
Once the reading has been taken, by pressing the button on the
control box briefly, the burner repeats the start cycle.
WARNING
If a timing of > 2 seconds occurs, delayed start-up is present.
Check the adjustment of the hydraulic brake of the gas valve,
the air damper and the combustion head adjustment.
37
Suggested remedy
Replace
Reduce the minimum gas pressure switch interven-
tion pressure. Replace the gas filter cartridge.
Interval
Signal
3 secs