SECTION 10 |
Protections
Power Surge Condition:
the rated output current for PST-600 or, 200% of the rated output current for PST-1000,
output current limiting is carried out instantly resulting in drop in the AC output voltage
(the drop is proportional to the load impedance). Surge Power of 166% for PST-600 and
Overload Condition:
latched in this shut down condition and will require manual reset. To reset, switch OFF the
again. Before switching ON, determine and remove the cause of overloading.
Short Circuit Condition: Short circuit condition will be detected when the AC output
will be shut down thereafter.
"POWER" (2, Fig 6.1) will continue to be lighted. The unit will be latched in this shut
down condition and will require manual reset. To reset, switch OFF the unit using the
switching ON, determine and remove the cause of short circuit.
10.2 WARNING ALARM - LOW DC INPUT VOLTAGE
minals due to voltage drop in the battery wires and connectors. The drop in the voltage
Please
see Section 8.4.3 "Connection from Batteries to the DC Input Side – Sizing of Cables and
Fuses"
available. This warning buzzer alarm indicates that the battery is running low and that
the inverter will be shut down after sometime if the voltage at the inverter terminals
lower for PST-600-24 / PST-1000-24.
10.3 LOW DC INPUT VOLTAGE SHUT DOWN
(2, Fig 6.1) will remain
42 | SAMLEX AMERICA INC.