SECTION 8 |
ruption of very high current will generate a hazardous, high temperature, high-energy
arc with accompanying high-pressure wave that may cause fire, damage nearby objects
and cause injury. To prevent occurrence of hazardous conditions under short circuit con-
ditions, the fuse used in the battery circuit should limit the current (should be "Current
time, quench the arc in a safe manner. For this purpose, UL Class T Fuse or equivalent
fast acting fuse will blow in less than 8 ms under short circuit conditions. Appropriate
capacity of the above Class T fuse or equivalent should be installed within 7" of the
battery Plus (+) Terminal (Please see Table 8.2 for fuse sizing). Marine Rated Battery
with ISO 8820-6 for road vehicles.
WARNING!
provide safety against fire hazard due to accidental short circuit in the battery
will NOT blow if there is a short circuit along the length of wires connecting the
battery and the inverter.
8.4.5 Recommended Sizes of Battery Cables and Fuses
Sizes of cables and fuses are shown in Table 8.2. Sizing is based on safety considerations speci-
Table 8.2 Recommended Sizing of Battery Cables and External Battery Side Fuse
Model No.
Maximum
Continu-
ous DC
Input
Current
(See
Note 1)
(1)
(2)
PST-600-12
80A
PST-600-24
40A
PST-1000-12
160A
PST-1000-24
80A
Installation
Minimum
External
Ampacity
Battery
of cable as
Fuse Size
per NEC
(Based on
(See
Column 2)
Note 2)
(See
Note 3)
(3)
(4)
100A
80A
40A
200A
160A
100A
80A
Minimum cable size
(See Note 4)
3 ft /
6 ft /
0.91M
1.83M
(5)
(6)
SAMLEX AMERICA INC. | 35
-
mandatory to
Part No.
of Recom-
mended
10 ft /
Samlex
3.05M
America
Inverter
Installa-
tion Kit
(See
Note 5)
(8)
(7)
KIT
KIT
KIT
KIT