SECTION 7 |
The discharge curves in Fig. 7.1 show the % State of Charge versus the terminal voltage
7.11 LOW DC INPUT VOLTAGE ALARM IN INVERTERS
TABLE 7.5 TERMINAL VOLTAGE AND SOC OF LOADED BATTERY
Discharge Current:
C-Rate
C/10 A
C/20 A
C/100 A
Amps. However, for lower C-Rate discharge current of C/10 Amps and lower, the battery
will be almost completely discharged when the alarm is sounded. Hence, if the C-Rate
discharge current is lower than C/5 Amps, the battery may have completely discharged
by the time the Low DC Input Alarm is sounded.
7.12 LOW DC INPUT VOLTAGE SHUT-DOWN IN INVERTERS
disconnect the battery to prevent further draining of the battery. If the load is not dis-
connected at this stage, the batteries will be drained further to a lower voltage and to a
completely discharged condition that is harmful for the battery and for the inverter.
Inverters are normally provided with a protection to shut down the output of the inverter
General Information on Lead Acid
Batteries
Terminal Voltage at 80% State
of Discharge (20% SOC)
12V
Terminal Voltage When Completely
Discharged (0% SOC)
24V
12V
21.8V
11.00V
SAMLEX AMERICA INC. | 23
-
24V
20.6V
22.0V
-
-