SECTION 8 |
NOTES FOR TABLE 8.2
install this fuse within 7" of the battery Positive terminal to protect the battery cables
against short circuit. Amp rating of the fuse is based on the following considerations:
b) Closest Standard Ampere Rating of Fuse has been used - Refer to NEC-2014
(National Electrical Code) - Section 240.6(A)
c) Where Standard Fuse Rating does not match the required Ampacity (Col-
NEC-2014 (National Electrical Code) - Section 240.4(B)
d) Type of fuse:
or equivalent
2 considerations. Thicker conductor out of the following 2 considerations has been
chosen:
air. Conductor size is based on:
b) Voltage drop across the length of cables limited to 2% of 12V / 24V.
(Column 2) and the resistance of the total length of Copper conductor (the
total length of conductor has been taken as 2 times the running distance
between the unit and the battery to cover 2 lengths of Positive and Negative
cable conductors).
ii) Resistance of the cable is based on Table 8.1.
ers and from 1200W to 7000W for 24V inverters. Please note that the Inverter Installation
ingly bigger fuse size than those recommended in Table 8.2. This is acceptable.
Fuse in the battery circuit is primarily required for protection against short circuit in
fuse used for protecting a battery cable against short circuit has to be lower than the
36 | SAMLEX AMERICA INC.