Indicator type BC-1-4 - Sectional View
Connection of the Outputs and the Potential-Free Relay Contacts on the Indicator
The indicator has 3 potential-free relay contacts.
The outputs Alarm 1 and Alarm 2 are intended for the actuation of external alarm units (for
the connection of the signalling or control devices of the overfill sensor).
The output Betrieb [Operation] is intended for connection of an external operation indicator
(lamp).
The outputs Alarm 1 and Alarm 2 are not monitored, i.e. a line disconnection or a short
circuit to the connected signalling or control devices is not recognised and indicated by the
measuring transducer.
Therefore, either the signalling and control devices must be switched in such a way that a line
disconnection is signalled (static current principle) or a functional control of the overfill sensor
(including the connected signalling and control devices with actuator) must be carried out
before each filling.
This can be done by pushing the Prüfen [Test] button at the measuring transducer – this
leads to an alarm signal, and possibly connected signalling and control devices are switched.
After release of the Prüfen [Test] button, the alarm signal goes out.
The indicated test does not replace the required annual test (see paragraph
MAINTENANCE).
Option 1: Connection of the Operation, Alarm1 and Alarm2 outputs to the supply voltage
maximum switching voltage 230V ~ 50Hz
Operation
Type of current
+ Alarm1
maximum switching current 1.0A
+ Alarm2
maximum switching power
During connection, additionally secure the indicator using a back-up fuse.
Option 2: Connection of the Operation, Alarm1 and Alarm2 outputs to the low voltage
maximum switching voltage 24V ~
Operation
Type of current
+ Alarm1
maximum switching current
+ Alarm2
maximum switching power
If one of the Operation, Alarm1 and Alarm2 connections is operated with SELV
(safety extra-low voltage) or PELV (protective low voltage) electrical circuits, it is also
the case that the others can only be operated with SELV and/or PELV or not
connected.
10 / 16
Overfill prevention divice type BC-1
AC
230VA
SELV/ PELV; AC
4.0A
96W
60V =
SELV/ PELV; DC
0.6A