[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
NOTE
It is therefore recommended to leave the auto restart
function enabled.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the pr button to enable the schedule timer again.
■ [3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
NOTE
If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.
[4] Space heating off temperature
Space heating off temperature
■ [4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.
[9] Cooling and heating set point ranges
The purpose of this field setting is to prevent the user from selecting
a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.
CAUTION
In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.
In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation (field setting of parameter [9-03]) to
16~18°C to prevent condensation on the floor.
■ [9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.
■ [9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
■ [9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.
■ [9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.
RKHBH/X008BA
Indoor unit for air to water heat pump system and options
4PW54225-1
[D] Local shift value weather dependent
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting "[1] Weather
dependent set point (heating operation only)" on page 11) is
selected.
■ [D-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
local shift value
range
[1-03]
[1-00]
0°C
[1-01]
T
Target water temperature
t
T
Outdoor temperature
A
range
Range
local shift
Local shift value
value
[1-00], [1-01],
Applicable field setting of the weather dependent set
[1-02], [1-03]
point [1]
Outdoor temperature range
(T
)
[D-03]
A
0
1
–2°C~2°C
2
3
–4°C~4°C
4
[E] Unit information readout
■ [E-00] Readout of the software version (example: 23)
■ [E-01] Readout of the EEPROM version (example: 23)
■ [E-02] Readout of the unit model identification (example: 11)
■ [E-03] Readout of the liquid refrigerant temperature
■ [E-04] Readout of the inlet water temperature
NOTE
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated
after looping through the field setting first codes
again only.
T
A
Local shift value
2
4
2
4