Detailed Description - Daikin ROTEX RKHBH008BA Manuel D'utilisation

Unité intérieure pour système de pompe à chaleur air à eau et options
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 52
6
Repeat step 2 through 4 to change other field settings as
required.
When finished, press the z button to exit FIELD SET MODE.
7
NOTE
Changes made to a specific field setting are only
stored when the pr button is pressed. Navigating to a
new field setting code or pressing the z button will
discard the change made.
Before shipping, the set values have been set as
shown under "Field settings table" on page 13.
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.

Detailed description

[0] User permission level
If required, certain user interface buttons can be made unavailable for
the user.
Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons pfi and pfj immediately followed by
simultaneously pressing buttons s and ba, and keeping all 4
buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].
Button
s
Quiet mode button
Weather dependent
ba
set point button
Schedule timer
pr
enable/disable button
<
Programming button
pf
i
Time adjust buttons
pf
j
Inspection/test
z
operation button
[1] Weather dependent set point (heating operation only)
The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.
■ [1-00] Low ambient temperature (Lo_A): low outdoor
temperature.
■ [1-01] High ambient temperature (Hi_A): high outdoor
temperature.
■ [1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.
■ [1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
Operation manual
11
Permission level
1
2
3
operable
operable
operable
operable
operable
operable
operable
T
t
Lo_Ti
Hi_Ti
Lo_A
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
= Shift value
[2] Disinfection function
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function field settings must be configured
by the installer according to local and national regulations.
■ [2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.
■ [2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).
■ [2-02] Start time: time of the day at which the domestic hot
water should be heated.
■ [2-03] Set point: high water temperature to be reached.
■ [2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
[2-03]
T
H
T
U
00.00
01.00
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
T
High set point temperature [2-03]
H
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local and national regulations.
Indoor unit for air to water heat pump system and options
+ 05
Shift value
00
– 05
Hi_A
T
A
[2-04]
22.00
23.00
24.00
t
[2-02]
RKHBH/X008BA
4PW54225-1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Rotex rkhbx008ba

Table des Matières