5. Commissioning, operation
Menu
Description
item
Reset delay time, at which the reset value
DR1/DR2
must be continuously present until an
EN
electrical signal change occurs (RP1 or
RP2)
OU1 / OU2
Switching function (switching output 1 / 2)
Damping (digital display)
AVGD
AVG1/AVG2
Damping (switching output 1 / 2)
AVG3
Damping (analogue signal)
UNIT
Unit switching
0SET
Zero point setting / Executing "Autozero"
(max. 3 % of span)
DISM
Display value in display mode
DISU
Refresh rate (digital display)
DISR
Rotate the indication by 180° (digital
display)
DRES
Resolution (digital display)
16
Parameter
0.00 ... 65.00 s
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
0.00 ... 65.00 s
0.00 ... 65.00 s
0.00 ... 65.00 s
BAR, mBAR, MPA, KPA, PSI, KGcm (kg/cm²), %
Yes / No
ACT = current system pressure
LOW, HIGH = min/max system pressure
OFF = display off
SP1/FH1 = set switching value
RP1/FL1 = set reset value
SP2/FH2 = set switching value
RP2/FL2 = set reset value
1, 2, 5, 10 updates/second
Yes / No
OPT = optimised (Stabilises the display of the
measured values, with rounding factors for the last
digit, optimised for the measuring range)
FULL = maximum (finest resolution, if required, for a
stable display of measured values a damping must
be set for the digital display)
WIKA operating instructions, model PSD-4-ECO
Factory setting
0.00 s
HNO
0.20 s
0.00 s
0.00 s
Order-related
ACT
5
OPT

Publicité

Table des Matières
loading