fi nish framing - after appliance installation
EN
single-sided recessed
Ceiling
minimum framing
Ref
K
E
F
J
L
M*
*Can only be increased to 4" max. by building a protrusion.
note:
The L series requires a minimum enclosure height of 73" (185.4cm) measured from the bottom of the appliance.
For temperature requirements, this area must be left unobstructed. Some venting confi gurations that require
more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and
combustibles. It is also recommended that the enclosure be ventilated at the top and bottom to circulate the
hot air.
44
W415-2033 / B / 02.04.20
L
M*
J
F
L38
39 15/16" (101.4cm)
17 15/16" (45.6cm)
53 13/16" (136.7cm)
Optional - Appliance does not need to be elevated above fl oor
73" (185.4cm)
3" (76mm)
note:
Shaded components (fi nish framing) must be
non-combustible materials.
Finish framing must be built after the appliance has
been placed in its fi nal position and venting
connected.
This confi guration also requires recess
area to use non-combustible facing due
to close proximity to vent.
K
Drywall
E
Insulation
L50
39 15/16" (101.4cm)
17 15/16" (45.6cm)
65 13/16" (167.2cm)
73" (185.4cm)
3" (76mm)