Electrical Connection - Baumer CombiTemp TCR6 Mode D'emploi

Masquer les pouces Voir aussi pour CombiTemp TCR6:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Mounting
The CombiTemp™ TCR6 can be mounted in more different ways.
1.
Sensor tube without connection
Baumer offers compression glands fitting Ø6 and Ø8 mm sensor diameter.
This type of mounting is normally used for mounting a sensor direct into a non-pressurized application. If pressurized, ensure that the
connection is tightened correct, so no leakage occur.
A duct channel mounting flange for 8 mm sensor is also available (type: ZPX1-002)
All threaded connection can be mounted direct into the application without thermowell, however often a thermowell is required to enable the user
to take out the sensor for e.g. calibration without opening the system.
2.
Sensor with male threaded process connection G 1/2 A
This G 1/2 A connection can be mounted in a Baumer thermowell type ZPT4.
The process connection available are R 1/2, G 1/2 A, G 3/4 A, M20×1,5
or with hygienic ISO 2852 clamp DN 38
3.
Sensor with male threaded process connection G 3/4 A and G 1 A and sensors with G 1/2 or G 3/4 female thread
For these connections a special thermowell can be supplied.
Mount the gland/pocket into the application and install the sensor after the gland/pocket is fixed to the application. This will ensure that the cable is
not twisted during mounting.
Baumer recommend to use a thermal compound filled into the thermowell ensure best possible heat transfer between the pocket and the Com-
biTemp TCR6.
Baumer offers a 6 gram bag Thermal compound, type ZPX1-001.

Electrical connection

Ceramic terminal block
Single element, 2-wire
Double element
Ambient temperature with ceramic block: -40...160°C
Cable sensor insert
Pt100
2-w
3-w
4-w
2-w
White White
Red
Red
www.baumer.com
Single element, 4-wire
Warning
Note: Check the maximum temperature for the cable used.
Operating instructions: 11119033 11
Operating instructions for temperature sensor
TCR6
Industrial temperature sensor
Temperature transmitter
Ambient temperature with built in transmitter: -40...85°C
M12 plug version
Transmitter:
Pin 1 = 4...20 mA +
Pin 3 = 4...20 mA -
Ceramic block, 2-wire:
Pin 1/2 = 1st wire
Pin 3/4 = 2nd wire
Ceramic block, 4-wire:
Pin 1 = 1st wire
Pin 2 = 2nd wire
Pin 3 = 3rd wire
Pin 4 = 4th wire
Pt100
2-w 4-w
3-w 2-w
-
+
4...20 mA
Ceramic block, double element
Pin 1 = Element 1, 1st wire
Pin 2 = Element 1, 2nd wire
Pin 3 = Element 2, 1st wire
Pin 4 = Element 2, 2nd wire
Page 3 / 14

Publicité

Table des Matières
loading

Table des Matières