9.8 - DIAGNOSTICS AND DEVICE SIGNALS

Certain devices are configured to display messages to identify their operating status or any anomalies.

9.8.1 - Photocell signals

The photocells contain a SAFE led (Fig. 32) that allows for verifying their operating status at any time: see
Table 8.
SAFE led (Fig. 32)
Status
Off
The photocell is not powered or is
faulty
3 quick flashes and 1
Device not recognised by the control
second pause
unit
1 very slow flash
The RX receives an excellent signal
1 slow flash
The RX receives a good signal
1 quick flash
The RX receives a poor signal
1 very quick flash
The RX receives a bad signal
Always lit
The RX does not receive any signal

9.8.2 - Flashing light signals

During the manoeuvre, the flashing light emits 1 flash each second; when there is an anomaly, it flashes quickly: see Table 9.
Flashes (quick)
Status
1 flash
Error on the ECSbus
1 second pause
1 flash
2 flashes
Intervention of a photocell
1 second pause
2 flashes
3 flashes
"Gearmotor force" limiting device
1 second pause
activated
3 flashes
4 flashes
Intervention of the Stop input
1 second pause
4 flashes

9.8.3 - Control unit signals

On the control unit there are LEDs (Fig. 8) that emit signals both during normal operation and in case of anomalies: see Table 10.
ECSbus led
Status
Off
Fault
On
Serious fault
1 flash per second
All OK
2 long flashes
Input status variation
1 flash every 5 seconds Automation in "standby" mode
Series of flashes sepa-
Flashing light signal see Table 9
rated by a pause
Quick flash
ECSbus short-circuit
Stop led
Status
Off *
Intervention of the Stop input
On
All OK
SbS led
Status
Off
All OK
On
Intervention of the SbS input
Led L4
Status
Off *
All OK
TABLE 8
Action
Check that the voltage on the photocell terminals is around 8–12 VDC; if the volt-
age is correct, the photocell is probably faulty
Repeat the recognition procedure on the control unit. Check that all pairs of pho-
tocells on the ECSbus have different addresses (consult the instruction manual of
the photocells)
Normal operation
Normal operation
Normal operation but check TX-RX alignment and correct cleaning of photocell
lenses
At the limit of normal operation; check TX-RX alignment and correct cleaning of
photocell lenses
Check for any obstruction between TX and RX. Check that the led on TX emits a
slow flash. Check the TX-RX alignment
TABLE 9
Action
At the beginning of the manoeuvre the devices present do not match those recog-
nised; check and, if necessary, try running the recognition procedure (Par. 9.2.1).
One or more devices may be faulty; check and, if necessary, replace them
At the start of the manoeuvre, one or more photocells do not enable movement;
check to see if there are any obstructions.
During the movement, if the obstacle is effectively present, no action is required
During the movement, the gate experienced excessive friction; identify the cause
At the start of the manoeuvre or during the movement, the Stop input intervened;
identify the cause
TABLE 10
Action
Verify whether there is power and whether the fuses are blown; in this case, iden-
tify the reason for the failure then replace them with others of the same type
There is a serious fault; try switching off the control unit for a few seconds; if the
condition persists, it means that there is a malfunction and the electronic circuit
board has to be replaced
Control unit works correctly
This is normal when there is a change in one of the inputs: SbS, Stop, intervention
of photocells or the radio transmitter is used
All OK; when a command arrives, the control unit will restore normal operation
(after a brief delay)
An overload has been detected therefore the power to the ECSbus was switched
off. To verify, disconnect one device at a time.
To activate power to the ECSbus, simply give a command (for example, through
the transmitter)
Action
Check the devices connected to the Stop input
Stop input active
Action
SbS input not active
Normal only if the device connected to the SbS input is actually active
Action
No Memorisation in progress
32
TX
RX
led
SAFE