Connecting Remote Controller, Indoor And Outdoor Transmission Cables; External Input/Output Function - Mitsubishi Electric CITY MULTI PWFY-P100VM-E-BU Manuel D'utilisation

Masquer les pouces Voir aussi pour CITY MULTI PWFY-P100VM-E-BU:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26
Model
PWFY-P140VM-E1-AU
PWFY-P140VM-E2-AU
2. Power cable specifications
Minimum wire thickness (mm
Model
Main cable
PWFY-P100VM-E-BU
2.5
Model
Total
operating
PWFY-P140VM-E1/E2-AU
current
[Fig. 10.1.1] (P. 6)
A Breaker for current leakage
B Local switch or breakers for wiring
C PWFY-P100VM-E-BU
D PWFY-P140VM-E1/E2-AU
E Pull box
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of malfunc-
tion or fire.
10.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote controller is optionally available.)
• Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield))
The "S" on unit TB5 is a shielding wire connection. For specifications about the
connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote control-
ler.
• Connect the "1" and "2" on unit TB15 to a MA remote controller. (Non-polarized
2-wire)
[Fig. 10.2.1] (P.6) MA Remote controller
• DC 10 to 13 V between 1 and 2 (MA remote controller)
[Fig. 10.2.2] (P.6) MA Remote controller
• The MA remote controller cannot be used at the same time or interchangeably.
A Non-polarized
C MA remote Controller
E TB2 (Power supply wiring)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
• Use wire with supplemental insulation.
• Input to TB142A, TB142B, and TB142C should not carry voltage.
• Cables from equipment connected to external input/output should have supple-
mental insulation.
• Use a single multiple-core cable for external input/output to allow for connection to
the PG screw.
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec-
tion, heating or fire result.

10.3. External input/output function

Preset temperature input (external analog input: 4mA-20mA)
External input is input through CN421, CN422 on the circuit board. (Fig. 10.3.1)
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature
changes with the current.
Refer to the instructions manual that came with the MA remote controller for how to
make the settings.
4 mA → 10 °C
20 mA → 70 °C
Note:
Use a 4-20 mA signal output device with insulation.
External output terminal
14
Power supply
Hz
Volts
50/60
220-230-240 V
50/60
220-230-240 V
)
2
Breaker for current leakage
branch
Ground
-
2.5
30 A 30 mA 0.1 sec or less
Minimum wire thickness (mm
Main cable
branch
16 A or less
1.5
1.5
25 A or less
2.5
2.5
32 A or less
4.0
4.0
B TB15 (MA remote controller cables)
D TB5 (Transmission cables)
Voltage range
MCA (A)
Max. 264 V
0.085
Min. 198 V
Max. 264 V
0.175
Min. 198 V
Local switch (A)
capacity
fuse
25
25
)
2
Breaker for current leakage
Ground
1.5
20 A 30 mA 0.1 sec. or less
2.5
30 A 30 mA 0.1 sec. or less
4.0
40 A 30 mA 0.1 sec. or less
External output terminal (refer to Fig. 10.3.2) is ineffective when the circuit is open.
Refer to Table 10.3.2 for information about each contact.
The current and voltage in the circuit to be connected to external output terminal
(TB141A OUT1) must meet the following conditions.
Contact rating
current
AC250V
1A or less
AC125V
3A or less
DC30V
3A or less
Table 10.3.2
OUT1*1
OUT2
OUT3*1
OUT4
*1 This function is available for PWFY-P100VM-E-BU.
External input terminal
The wire length must be within 100 m.
External input terminal (refer to Fig. 10.3.3) is ineffective when the circuit is open.
Refer to Table 10.3.3 through Table 10.3.5 for information about each contact.
Only the "pump interlock" function is ineffective when the circuit is short-circuited.
Connect a relay circuit to the external output terminal as shown in Fig. 7.4.1.
The specifications of the relay circuit to be connected must meet the following condi-
tions.
Contact rating voltage
DC15V
Contact rating current
0.1A
Minimum applicable load
1mA at DC
Table 10.3.3
<PWFY-P100VM-E-BU>
TB142A
IN1
<PWFY-P140VM-E1/E2-AU>
TB142A
IN1
Table 10.3.4
TB142B
IN3
Connection demand
IN4
Table 10.3.5
TB142C
COM+
IN5*1
IN6*2
IN7*3
IN8*5
*1 PWFY-P100VM-E-BU
PWFY-P140VM-E1/E2-AU
*2 Effective when SW 4-3 is set to ON.
*3 Effective when SW 4-4 is set to ON.
*4 When setting Heating ECO or Anti-Freeze mode, reset all power supply of all
units (outdoor/indoor units).
*5 This function is available for PWFY-P140VM-E1/E2-AU.
RLA (A)
Cooling
0.068-0.065-0.063
0.138-0.139-0.140
Breaker for wiring (NFB) (A)
30
Local switch (A)
Breaker for wiring
(NFB) (A)
capacity
fuse
16
16
25
25
32
32
Operation ON/OFF
Defrost
Compressor
Error signal
Pump interlock
Flow switch
Operation ON/OFF
Common
Hot Water/Heating
Heating ECO
Anti-freeze
Cooling
Hot Water
Heating
Heating
20
30
40