Cable types and minimum thicknesses
Connection
230 V AC power-supply to control panel
Encoder gearmotor power supply*
Power supply to gearmotor**
Flashing light
Photocell transmitters
Photocell receivers
Command and safety device
Endstop***
Antenna
Encoder****
* AXO ** FROG-A24, F4024, F1024, FROG-A24E, F7024E *** FROG-A24, F4024, F1024 **** FROG-A24E, F7024E, F4024E
 If cable lengths diff er from those specifi ed in the table, establish the cable sections depending on the actual power draw of the connected
devices and according to the provisions of regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual power draw and
distances. For connecting products that are not contemplated in this manual, see the literature accompanying said products
INSTALLATION
Fasten the control panel in a protected area using suitable screws. anchors and braces.
Drill through the pre-perforated holes and fit the cable gland with corrugated pipes for passing through the electric cables.
 Pre-perforated hole diameter: 20 mm.
Assemble the pressure hinges.
Fit the hinges into the box (either on the right or left) and fasten them using the supplied screws and washers.
Snap the cover onto the hinges. Close it and secure it using the supplied screws.
After performing the settings and adjustments, fasten the cover using the supplied screws.
Cable length
Cable type
1 < 15 m
H05RN-F
3G x 1.5 mm
3 x 1.5 mm
2 x 1.5 mm
FROR CEI 20-22
CEI EN
50267-2-1
the RG58 antenna
2402C 22AWG
Cable length
15 < 30 m
2
2
3G x 2.5 mm
2
2
3 x 2.5 mm
2
2
2 x 2.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
4 x 0.5 mm
2
2 x 0.5 mm
2
3 x 1.5 mm
max 10 m
max 30 m
slide to rotate
15 mm~