3.2 Putting the devices online

After having completed hardware installation, is devices must be put on line to let boss recognise the devices
connected to the serial ports. After the devices are on line, check each device status in the details page and
continue with system confi guration.
Note: Default settings are already installed in boss for standard CAREL devices. Once online, the main
variables and log variable data can be viewed and alarms managed.
For each serial line: under Confi guration à Site
1.
confi guration click È Add and set the features
of the serial line. To select the COM port, if the
USB-RS485 converter is used (available function
only with boss, and NOT with boss-mini), follow
the automatic recognition procedure. If there are
CAREL devices on the line, these will be recognised
automatically using the automatic function,
otherwise proceed with points 2-3.
2.
Choose the type of device.
3.
Add physical devices to the line either individually
or by address range
4.
Customise the description of each individual
device.
5.
Repeat the entire procedure for other lines.
In Plant à Devices displays the list of all fi eld
6.
devices.
7.
Check color around the device image = device
status
(green). Device connected and operating.
(black). Device not connected.
(blue). Device connected but disabled.
(red). Device alarm.
Note: To stop receiving alarms from a device: under Confi guration à Site confi guration à Site, click
the line and click on Modify check the device to be disabled and then click Save.
Nota: To delete alarms and events generated when putting the devices on line: under Confi guration
à System pages àSystem click Clear list of alarms and events
+040000260 - 1.1 - 06.03.2019