4. HOW TO INSTALL THE UNIT

Minimum operation and maintenance area. (fig. 4-1)
Fig. 4-1

4-1 Suspending the Unit at the Ceiling

This unit uses a drain pump. Use a carpenter's level to check
that the unit is levelled.
Determine the pitch of the suspension bolts
provided full-scale installation diagram
The full-scale diagram must be placed in the centre between
the "T" bars; the "T" bar
components box
must be removed temporary. Unit must be
installed in false ceiling only. (fig. 4-2)
Before installing the unit, place the tubes, the electrical
wires and the condensate drain pipe in the proper position
for the connection.
Adjust the distance between the unit and the ceiling
23 mm) using the nuts of the four suspension bolts.
Verify also the distance between the suspension bracket
and the ceiling
(min 41 mm); a smaller distance can cause
noise in case the unit touches the ceiling.(fig. 4-3)

4-2 Installation of the condensate drain pipe

Utilise a hard, well insulated PVC pipe
it to the unit using a flexible PVC or gummy hose
firmly with hose bands
.
The connection must be well insulated, using foamed
polyethylene
(thickness 8mm). (fig. 4-4)
• If it is necessary to increase the height of the drain pipe
somewhat, the portion directly after the connection port can
be raised a maximum of 25 cm. Do not raise it any higher
than 25 cm
, as this could result in water leaks. (fig. 4-5)
• Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be allowed
to hang unsupported from its connection to the unit. Fasten
the pipe to a wall, frame, or other support
unit as possible. (fig. 4-6)
• Do not install an air bleeder
spray from the drain tube outlet. (fig. 4-7)
• Do not install pipe with an upward gradient
connection port. It will cause the drain water to flow
backwards and leak when the unit is stopped. (fig. 4-8)
• Be sure to provide insulation for any drain piping installed
indoors.
Drill a 65 mm diameter hole, insert a PVC pipe. (fig. 4-9)
using the
.
on the side of the electrical
(max
(I.D. 18 mm) and fix
; tighten
as close to the
, as this may cause water to
from the
Fig. 4-3
6
EG
Fig. 4-2