IMPORTANT !
When the unit is out of service, dr ain all the water
contents from the circuits.
If the dr aining operati on is felt to be too much trouble, ethyl ene glycol
may be mi xed with the water in suitabl e proportions in order to
guarantee protec tion from freezing. In the cas e of a small water flow in
the rej ection exc hanger operating as evapor ator, and/or an excessi vel y
low inl et temperature, the ST 3 pr obe could trigger the antifreeze alar m.
If the mac hine is i nstalled in a glyc ol and water loop, it is possible to
modify the s et point (using the pass word) on the basis of the
percentage of glyc ol us ed (s ee the table below).
IMPORTANT !
Mixing the wat er with glycol modifies the
performance of the unit.
The table bel ow gives the pr oporti ons of ethylene glycol whic h are
required to gi ve frost protec tion in a range of c onditions M aximum
ethylene gl ycol c ontent 30%.
% glycol in weight
10 %
Freezing
-5
temperature °C
II.6

ELECTRICAL CONNECTIONS

DANGER !
Always install a general automatic swit ch in a
protected ar ea n ear the appliance with a
characteristic d elayed curve, sufficient capacit y and
breaking po wer. There should be a m inimum
distance of 3 mm bet ween the contacts.
Earth connection is compulsor y b y law and
safeguard s the user wh ile the machine is in use.
DANGER !
Electrical connection of the unit must be car ried out
by personn el skilled in the matter and in
complian ce with the regulations in effect in the
country wher e the unit is inst alled . Non-conforming
electrical connection relieves RHOSS S.p.a. from all
responsibilit y for damage to persons and propert y.
In making the electrical connections to the board,
cables mu st be routed so that they do not touch the
hot parts of the mach ine (compr essor, flo w pip e
and liquid lin e). Protect the wir es from an y foam.
IMPORTANT !
For electrical conn ections to the unit and the
accessories, follo w the wir ing diagr ams wh ich are
supplied with them.
The safety door interloc k automaticall y prevents elec tric power being
fed to the unit if the c over panel over the el ectrical panel is opened.
After opening the front panel of the unit, feed the suppl y c ables through
the appropriate cable cl amps in the external panelling and then through
the ducts at the base of the elec tric board.
The el ectrical power supplied by the single-phase or thr ee-phase line,
must be taken to the main is olator s witc h.
The suppl y c able must be of the flexibl e type, with PVC s heathi ng of no
lighter than H05RN-F: for the sec tion, refer to the table below or the
wiring diagram.
Single-phase models (230V-1ph-50Hz)
Cable section
Line s ection
PE sec tion
Remote c ontrol s ection
15 %
20 %
25 %
-7
-10
-13
105
107
109
mm²
4
6
6
mm²
4
6
6
mm²
1,5
1,5
1,5
Cable section
Line s ection
PE sec tion
Remotecontrol s ection
The earth c onductor must be longer than the other conduc tors in order
to ensure that in the event of the cable cl amping devic e becoming
slack, it will be the last to c ome under strain.
II.6.1.1
Remote management using connections set
up by the installer
The connections between board and switc h or remote light must be
made with screened cable c onsisting of 2 twisted 0.5 mm² wires and the
screening. The screening must be connected to the earth screw on the
panel (on one side onl y). The maximum permitted distance is 30 m.
SCR - Remote ON/OFF control sel ector.
SEI - Summer/winter sel ector.
LBG - General loc kout light.
• Remote ON/OFF en ablem ent (SCR)
30 %
-16
Remove the ID8 terminal bridge on the elec tronic boar d and c onnect
the wires c omi ng from the remote control ON/OFF selec tor (selector to
be ins talled by the installer).
ATTENTION
• Remote summ er/winter enab lem ent on THAEY
Connect the wires c omi ng from the remote summer/winter selec tor on
the ID7 terminal pres ent on the electronic board.
At this poi nt, c hange parameter SUr from n to y .
ATTENTION
• LBG remote control
To remotel y c ontrol the two signals, c onnect the two l amps acc ording to
the i nstructions pr ovided in the wiring diagram supplied with the
mac hine ( max. 24 Vac 0,5A AC1).
II.6.1.2
Remote management using accessories
supplied separately
It is possible to remotel y control the entire machi ne by linking a second
keyboard to the one built into the mac hine (KTR acc essor y).
To select the remote c ontrol s ys tem, c ons ult paragraph II.2. The us e
and installation of the remote control s ystems are described i n the
Instruction Sheets provided with the same.
II.7
START-UP INSTRUCTIONS
112
10
10
1,5
32
SECTION II: INST ALL ATION AND MAINTEN ANCE
Three phase mod els (400V-3ph+N-50Hz)
107
mm²
2,5
mm²
2,5
mm²
1,5
IMPORTANT !
When the unit is switched OFF using the remote
control selector, the letter s Scr app ear on the on
board control panel disp lay.
Open contac t:
Closed c ontact:
Open contac t:
Closed c ontact:
IMPORTANT !
Machine commissioning or the first start up (wh ere
provided for) must be car ried out b y skilled
personnel from workshops authorised b y RHOSS
S.p.A., qualified to wor k on this t yp e of product.
IMPORTANT !
The use and maintenance m anual for the pump s is
enclosed with this manual and mu st be r ead
completely (only for P models).
DANGER !
Before starting up, m ake sur e that the in stallation
and electrical connections conform with the
instructions in the wiring diagram . Also make sure
that there ar e no unauthorised per sons in the
vicinit y of the machine dur ing the above oper ations.
109
112
2,5
4
2,5
4
1,5
1,5
the unit is OFF.
the unit is ON.
heating cycl e.
cooling c ycle.